Download Print this page

Viking VK192 Technical Data Manual page 3

Standard response large orifice dry concealed pendent sprinkler 8.0k

Advertisement

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Sprinkler
Sprinkler Nominal
Temperature
Classification
Ordinary
Intermediate
Intermediate
Cover Plate Finishes: Polished Chrome, Painted White, Painted Ivory, or Painted Black
The sprinkler temperature rating is stamped on the deflector.
1
Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
2
Refer to specific installation standards.
Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
3
The 135 °F (57 °C) cover has an orange label. The 165 °F (74 °C) cover has a white label.
4
Figure 2:
Sprinkler Installation and Correct Use of Sprinkler Wrench 07565W/B
Form No. F_081311
19.06.24
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Maximum Ambient
Temperature
Rating
Temperature
1
155 °F (68 °C)
100 °F (38 °C)
175 °F (79 °C)
150 °F (65 °C)
200 °F (93 °C)
150 °F (65 °C)
Rev 19.1
TECHNICAL DATA
Temperature Rating of the
Ceiling
Cover Assembly (Required)
2
135 °F (57 °C)
165 °F (74 °C)
165 °F (74 °C)
Footnotes
STANDARD RESPONSE
LARGE ORIFICE DRY
CONCEALED PENDENT
SPRINKLER VK192 (8.0K)
Cover Plate
Base Part
4
Number
3
12381
12381
12381
Page 3 of 5
Bulb
Color
Red
Yellow
Green

Advertisement