AFFINITY SINGLE STAGE HYDRONIC WITH OPTIHEAT INSTALLATION MANUAL
Operating Parameters cont.
Cooling Mode
Entering
Load Temp (
o
F)
Source Temp (
50
70
90
110
Notes: Operating parameters at 3 gpm/ton source and load flow.
Consult the Capacity Tables for each 504W11 OptiHeat model for normal allowable operating conditions.
Some of the conditions shown above are outside of the compressor operational limits for specific models.
Entering
Suction
o
F)
Pressure (psig)
30
86-99
50
92-107
70
98-115
90
101-119
110
105-122
30
89-106
50
103-125
70
118-143
90
125-151
110
135-155
30
92-113
50
115-143
70
129-158
90
145-165
110
160-180
30
96-121
50
127-161
70
158-200
90
155-175
110
170-195
Discharge
Superheat
Pressure (psig)
(
135-160
12-22
191-214
10-19
248-268
5-15
335-367
6-15
425-465
8-16
131-163
15-20
194-223
11-15
257-273
11-15
344-381
8-12
280-315
8-16
128-166
15-20
197-233
11-15
266-294
11-15
350-390
20-30
360-400
25-35
125-170
55-65
200-243
41-52
275-315
21-38
360-400
30-40
460-500
25-35
40
Subcooling
o
F)
(
o
F)
2-15
4-15
6-16
8-16
10-19
3-6
6-9
9-12
12-14
10-19
3-6
6-9
9-12
8-19
7-16
2-20
4-18
8-19
5-15
5-15
7/8/2014