Lennox EL297UH045XV36B Unit Information page 112

Hide thumbs Also See for EL297UH045XV36B:
Table of Contents

Advertisement

Troubleshooting: Heating Sequence of Operation Continued
2 STAGE THERMOSTAT
RECOGNITION DELAY
(30 SECONDS)
ONLY FOR 1ST
REQUEST FOR
2ND STAGE HEAT
1
SYSTEM WILL ALWAYS LIGHT ON LOW FIIRE, EVEN IF 2ND STAGE HEAT IS IN PLACE.
2
WHEN USED WITH A SINGLE STAGE THERMOSTAT, SET SW1 TO THE ON POSITION IN DIP SWITCH S4.
3
IF THE HIGH FIRE PRESSURE SWITCH DOES NOT CLOSE WITHIN 5 ATTEMPTS, THE SYSTEM WILL OPERATE AT
LOW FIRE FOR THE REMAINDER OF THE CALL FOR HEAT REQUEST.
CALL FOR SECOND-STAGE HEAT
2
CALL FOR 2ND STAGE HEAT
(HIGH FIRE)
SINGLE STAGE
THERMOSTAT
2ND STAGE
EXPIRED?
YES
YES
INDUCER SWITCHED
TO HIGH SPEED
HIGH
PRESSURE SWITCH
CLOSED WITHIN 10
SECONDS?
YES
2ND STAGE GAS VALVE
ENERGIZED
INDOOR BLOWER ENERGIZED
ON HIGH HEAT SPEED
3
CALL FOR HEAT SATISFIED
1
2
ON DELAY
EXPIRED?
INDUCER SWITCHED
NO
TO LOW SPEED
Page 112
5 MINUTE DELAY
3
(ERROR CODE FLASHES)

Hide quick links:

Advertisement

Table of Contents
loading