Drying Mode; Forced Operation Function; Sleep Function; Auto-Restart Function - Midea AURORA ONOFF Series Service Manual

Table of Contents

Advertisement

• time on to auto mode;
• the compressor doesn't start in 20 minutes when a
running mode is set in auto.
3.7

Drying mode

• Compressor will run for 10 minutes and be off for 5
minutes and loop again and again
• Indoor fan speed is fixed at low and can't be changed.
The louver angle is the same as in cooling mode.
• All protections are active and the same as that in
cooling mode.
• Low indoor room temperature protection
• If T1<10°C(50°F)., the compressor ceases operation
until T1>13°C(55.4°F)..
3.8

Forced operation function

Press the AUTO/COOL button, the AC will run as below
sequence:
Forced auto →Forced cooling →Off
• Forced cooling mode:
The compressor and outdoor fan continue to run and
the indoor fan runs at low speed. After running for 30
minutes, the AC will switch to auto mode with a preset
temperature of 24°C(76°F).
• Forced auto mode:
Forced auto mode operates the same as normal auto mode
with a preset temperature of 24°C(76°F).
• The unit exits forced operation when it receives the
following signals:
• Switch on
• Switch off
• Timer on
• Timer off
• Changes in:
• mode
• fan speed
• sleep mode
• Follow me
3.9

Sleep function

• The sleep function is available in cooling, heating, or
auto mode.
• The operational process for sleep mode is as follows:
• When cooling, the temperature rises 1°C(2°F) (to
• When heating, the temperature decreases 1°C(2°F)
• The operating time for sleep mode is 8 hours, after
which, the unit exits this mode but does not switch
off.

3.10 Auto-Restart function

• The indoor unit has an auto-restart module that
allows the unit to restart automatically. The module
automatically stores the current settings (not including
the swing setting) and, in the case of a sudden power
failure, will restore those setting automatically within 3
minutes after power returns.
• If the unit was in forced cooling mode, it will run in
this mode for 30 minutes and turn to auto mode with
temperature set to 24°C(76°F).
• If there is a power failure while the unit is running, the
compressor starts 3 minutes after the unit restarts. If
the unit was already off before the power failure, the
compressor starts 1 minute after the unit restarts.

3.11 Refrigerant Leakage Detection

With this new technology, the display area will show "EC"
when the outdoor unit detects refrigerant leakage.

3.12 Ionizer/Plasma (for some models)

When AC powers on and indoor fan is on, press "Fresh"
on the remote control to enable the IONIZER function.
While this function is active, the Ionizer/Plasma Dust
Collector(depending on models) is energized and will help
to remove pollen and impurities from the air.
Product Features 7
not higher than 30°C(86°F)) every hour. After 2
hours, the temperature stops rising and the indoor
fan is fixed at low speed.
(to not lower than 17°C(62.6°F)) every hour. After
2 hours, the temperature stops decreasing and the
indoor fan is fixed at low speed. Anti-cold wind
function takes priority.