3-3. Network converter (UTY-VGGXZ1)

¢ Accessory
Name and shape
Cable tie
Screw (M4 × 20 mm)
Dust proof bushing
Installation manual
3-3. Network converter (UTY-VGGXZ1)
For connecting single split type system (DIP switch setting is neces-
sary.)
With this Network converter, single split type and multi system air con-
ditioners can be controlled by System controller, Touch panel con-
troller, Central remote controller in VRF network system or by Wired re-
mote controller connected to the Network converter.
Start/Stop, operation mode, temperature setting, fan speed, etc. can be
done with these controllers.
One Network converter can be connected and controlled up to 16 in-
door units.
Two Wired remote controllers are possible for one Network converter.
Up to 100 Network converters can be connected in one VRF network
system. (One Network converter is regarded as one refrigerant system.
Total refrigerant systems in one VRF network system must be within
100.)
For connecting Group remote controllers
Up to a total of 16 Network converters, Central remote controller and
Touch panel controller can be connected in 1 VRF network system.
4 Group remote controllers can be connected to 1 Network converter.
2 refrigerant systems can be covered by 1 Network converter.
Q'ty
4
4
1
1
For mounting the power supply cable, remote controller
cable, and transmission cable
For mounting the Network converter
For connecting the power supply cable