CLEARPOINT
®
water separator
The direction of flow of the separator must be taken into account during set up. It must be adapted to the direction of
flow in the pipe.
Direction of flow
Left » right (default)
3
The housing head and the housing body are equipped with a double-start trapezoidal thread. The direction of flow of the
separator can be adapted to the direction in the pipe by turning the housing head through 180°. The direction of flow is
indicated by arrows [2] and a raised marking [3] on the housing head. These must be aligned as shown. The safety slide
[1] must always be in an easily accessible position on the front.
The fitting of a bypass pipe [4] and corresponding shut-off valves [5] is recommended for maintenance and servicing
work.
1. Apply sealing material e.g. PTFE-tape (EN 837-2) to the pipe ends
2. Screw the pipe thread into the separator outlet until the connection is firm and leak-tight
3. Screw the pipe thread into the separator outlet until the connection is firm and leak-tight
After assembly work has been finished, it must be checked whether the housing body has been screwed in properly,
the safety slide pushed up and the safety screw tightened hand-tight. A leakage test should be carried out to check the
assembly work. For additional information, refer to "9.6 Leakage test" on Page 39.
28 | 56
2
1
4
5
Installation and operation manual
Direction of flow
Right » Left
2
3
1