LG ART COOL LA181HSV5 Engineering Manual page 58

Single zone mirror wall mounted 3/4 to 2 tons
Table of Contents

Advertisement

PLACEMENT CONSIDERATIONS
Installing Outdoor Units Indoors
Open Rate by Louver Radian
Figure 44: Open Rate by Louver Radian Formula.
ho
≤ 15
ho = h * COS
Total Area (A) = H * W
Number of Open Spaces (N) = (Number of Louvers - 1)
Effective Area (Af) = ho * W * N
Louver Open Rate (n) = Af / A
Af = A * n
Effective Cross Section Area
Confirming Air Flow Rate / Total Opening Rate
• Example: LSU181HSV5.
• Discharge Airflow Rate: 2,119 ft.
• Velocity of Outlet Air: 15.1 ft./s
• Velocity of Inlet Air: 6.5 ft./s
• Open Rate = 80% or More
Open Rate = Effective Face Area (Af)
Total Face Area (A)
• Inlet airflow must match or exceed discharge airflow.
• Separate inlet airflow from discharge airflow to
prevent recirculation.
Formula
• Total Louver Dimension (Excluding Frame) (A) = 3.9 feet x 6.2 feet = 24.2 ft.
• Area Blocked by Outdoor Unit (Discharge) (B) = 2.6 feet x 2.8 feet = 7.41 ft.
• Inlet Louver Dimension (A - B) = 16.8 ft.
• Equivalent Inlet Dimension (Open Rate 80%) = 16.8 ft.
• Equivalent Inlet Airflow = 13.44 ft.
• Equivalent Inlet Airflow / Discharge Airflow = 5,241 ft.
58 | APPLICATION
h
Figure 45: Example of Installing Outdoor Unit Indoors.
Louver Dimensions
/min.
3
Unit: Inch
2
x 0.8 = 13.44 ft.
2
x 6.5 ft./s x 60 sec./min. = 5,241 ft.
2
/min. / 2,119 ft.
3
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
W
Side View
Front View
Air Guide Duct on
Outdoor Unit
55-1/8
47-1/4
2
2
2
/min.
3
/min. = 247% (Within Allowable Limits)
3
H
Outdoor Unit
Dimensions
34-1/4

Advertisement

Table of Contents
loading

Table of Contents