Heating Capacity Table for LA181HSV5 (LSU181HSV5 + LAN181HSV5)
Table 20: LSU181HSV5 / LAN181HSV5 Heating Capacities.
Outdoor Air
Temp.
60
°F DB °F WB
TC
PI
-3
-4
11.02
1.15
0
-1
11.99
1.27
1
0
12.15
1.28
6
5
12.69
1.32
10
9
13.25
1.37
16
14
13.67
1.38
17
15
13.76
1.40
19
17
13.95
1.42
24
23
15.30
1.48
32
30
18.34
1.59
41
38
21.04
1.70
43
40
21.72
1.73
47
43
22.73
1.76
53
50
22.96
1.78
59
53
23.48
1.80
64
57
23.98
1.84
70
61
24.43
1.86
75
65
24.77
1.89
DB: Dry Bulb Temperature (°F) WB: Wet Bulb Temperature (°F) TC: Total Capacity
(kBtu/h)
PI: Power Input (kW) (includes compressor, indoor fan motor, and outdoor fan motor)
1. All capacities are net, evaporator fan motor heat is deducted.
2. Direct interpolation is permissible.
Capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant piping.
Indoor Air Temperature: °F DB / °F WB
64
68
TC
PI
TC
PI
TC
10.68
1.14
10.58
1.14
10.47
11.63
1.25
11.51
1.25
11.40
11.78
1.27
11.66
1.27
11.54
12.31
1.31
12.18
1.31
12.06
12.85
1.35
12.72
1.35
12.59
13.25
1.37
13.12
1.37
12.99
13.34
1.38
13.21
1.38
13.08
13.52
1.41
13.39
1.41
13.25
14.83
1.46
14.68
1.46
14.54
17.78
1.58
17.60
1.58
17.43
20.40
1.68
20.20
1.68
20.00
21.06
1.71
20.84
1.71
20.64
22.04
1.75
21.82
1.75
21.60
22.26
1.76
22.03
1.76
21.82
22.77
1.78
22.54
1.78
22.31
23.25
1.82
23.02
1.82
22.79
23.69
1.84
23.45
1.84
23.22
24.02
1.87
23.78
1.87
23.54
Do not extrapolate.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
PERFORMANCE DATA
70
72
75
PI
TC
PI
TC
1.13
10.39
1.13
10.18
1.24
11.31
1.24
11.08
1.25
11.46
1.25
11.23
1.30
11.97
1.30
11.73
1.34
12.50
1.34
12.24
1.35
12.89
1.35
12.63
1.37
12.98
1.37
12.72
1.40
13.15
1.40
12.89
1.45
14.43
1.45
14.14
1.56
17.29
1.56
16.95
1.67
19.84
1.67
19.44
1.69
20.48
1.69
20.07
1.73
21.43
1.73
21.00
1.75
21.65
1.75
21.21
1.76
22.14
1.76
21.70
1.80
22.61
1.80
22.16
1.83
23.04
1.83
22.58
1.85
23.36
1.85
22.89
0 ft. level difference between outdoor and indoor units.
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and
60ºF wet bulb (WB), and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet
bulb (WB).
Heating Capacity
86
PI
TC
PI
1.12
9.94
1.12
1.23
10.82
1.23
1.24
10.96
1.24
1.29
11.45
1.29
1.33
11.95
1.33
1.34
12.33
1.34
1.35
12.41
1.35
1.38
12.58
1.38
1.43
13.80
1.43
1.55
16.54
1.55
1.65
18.98
1.65
1.67
19.59
1.67
1.71
20.51
1.71
1.73
20.71
1.73
1.75
21.18
1.75
1.78
21.63
1.78
1.81
22.04
1.81
1.83
22.35
1.83
PRODUCT DATA | 45