Tripp Lite AGPS5542 Owner's Manual page 7

Rack/tower mount on-line ups systems
Table of Contents

Advertisement

Available languages

Available languages

Installation
3
EPO Port Connection
This optional feature is only for those
applications requiring connection to a facility's
Emergency Power Off (EPO) circuit. When the
UPS is connected to this circuit, it enables
emergency shutdown of the UPS inverter and
inhibits transfer to internal bypass. Using the
provided cable, connect the UPS EPO port
to a user-supplied, normally-closed or
normally-open switch according to the circuit
3b
diagram
.
Note:
1. If using a cable other than what is supplied, the
cable should not exceed 350 feet or have a
resistance of greater than 10 ohms.
2. If a non-latching EPO switch is used, the EPO
must be held for a minimum of 1 second. This
does not apply to a latching EPO switch.
CAUTION: The EPO port is not a
phone line surge suppressor; do
not connect a phone line to this
port.
UPS Unit State when asserting EPO with AC line present:
LEDs
OFF
To restart the UPS unit after asserting EPO with AC line present:
Option 1:
1. Verify that the EPO assertion has been removed or cleared.
2. Press OFF button until you hear a click (approx. 1 second).
3. Press ON button and UPS output will turn back on.
Option 2:
1. Verify that the EPO assertion has been removed or cleared.
2. Remove AC line power to the UPS unit.
3. Reapply AC line power. Now the UPS will start back up in normal operation mode.
UPS Unit State when asserting EPO without AC line power:
LEDs
OFF
To restart the UPS unit after asserting EPO without AC line power:
1. Verify that the EPO assertion has been removed or cleared.
2. Reapply AC line power to the UPS unit. Now the UPS will start back up in normal operation
mode.
17-05-032-932471.indb 7
3a
Output
Fans
OFF
ON
Output
Fans
OFF
OFF
3a
Your model may differ.
3b
Serial
SNMP
ON
ON
Serial
SNMP
OFF
OFF
7
4-5
USB
ON
USB
OFF
5/23/2017 1:41:45 PM

Advertisement

Table of Contents
loading

Table of Contents