Westinghouse WGen7500 - Portable Generator Manual

Westinghouse WGen7500 - Portable Generator Manual

Also See for WGen7500:

Advertisement

Contents
Westinghouse WGen7500 - Portable Generator Manual

INTRODUCTION


Operating, servicing, and maintaining this equipment can expose you to chemicals including engine exhaust, carbon monoxide, phthalates, and lead, which are known to the State of California to cause cancer and birth defects or other reproductive harm. To minimize exposure, avoid breathing exhaust, and wear gloves or wash your hands frequently when servicing this equipment. For more information go to www.P65warnings.ca.gov.

DISCLAIMERS
All information, illustrations, and specifications in this manual were in effect at the time of publishing. The illustrations used in this manual are intended as representative reference views only. We reserve the right to make any specification or design change without notice.

ALL RIGHTS RESERVED
All rights reserved. No reproduction allowed in any form without written permission from Westinghouse Outdoor Power Equipment, LLC.


Read this manual before using or performing maintenance on this product. Failure to follow the instructions and safety precautions in this manual can result in serious injury or death.
SAVE THESE INSTRUCTIONS

SPECIFICATIONS

Running Watts: 7500
Peak Watts: 9500
Rated Voltage: 120/240V
Rated frequency: 60 Hz @ 3600 RPM
Phase: Single phase
Total Harmonic Distortion: ≤ 23%
Engine Displacement: 420 cc
Starting Type: Recoil, Electric Start, Remote
Fuel Capacity: 6.6 Gallons (25 Liters)
Fuel Type: 87–93 octane*
Oil Capacity: 1.16 Quart (1.1 Liter)
Oil Type: SAE 10W-30
Spark Plug: F7TC
Spark Plug Gap: 0.024 – 0.032 in.
(0.60 – 0.80 mm)
Valve Intake Clearance: 0.0031 – 0.0047 in.
(0.08 – 0.12 mm)
Valve Exhaust Clearance: 0.0051 – 0.0067 in.
(0.13 – 0.17 mm)
AC Grounding System: Neutral bonded to frame
Voltage Regulator: AVR
Alternator Type: Brushed
Maximum Ambient Temperature: 104°F (40°C)
Certifications:
  • EPA
  • CARB
  • CSA

*Ethanol content of 10% or less. DO NOT use E15 or E85.

warning NOTICE
This product is designed and rated for continuous operation at ambient temperatures up to 104°F (40°C). If needed, this product can be operated at temperatures ranging from 5°F (15°C)–122°F (50°C) for short periods. If the product is exposed to temperatures outside of this range during storage, it should be brought back within this range before operation. This product must ALWAYS be operated outdoors in a well-ventilated area and far away from doors, windows, and other vents.

Maximum wattage and current are subject to and limited by such factors as fuel BTU content, ambient temperature, altitude, engine conditions, etc. Maximum power decreases about 3.5% for each 1,000 feet above sea level, and will also decrease about 1% for each 10°F (6°C) above 60°F (16°C) ambient temperature.

SAFETY

SAFETY DEFINITIONS

The words DANGER, WARNING, CAUTION, and NOTICE are used throughout this manual to highlight important information. Make sure that the meanings of this safety information is known to all who operate, perform maintenance on, or are near the generator.

warning This safety alert symbol appears with most safety statements. It means attention, become alert, your safety is involved! Please read and abide by the message that follows the safety alerts symbol.


Indicates a hazardous situation which, if not avoided, will result in death or serious injury.


Indicates a hazardous situation which, if not avoided, could result in death or serious injury.


Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.

warning NOTICE
Indicates a situation which can cause damage to the generator, personal property, and/or the environment, or cause the equipment to operate improperly.

warning Note: Indicates a procedure, practice or condition that should be followed for the generator to function in the manner intended.

SAFETY SYMBOLS

Follow all safety information contained in this manual and on the generator.

Symbol Description
warning Safety Alert Symbol
Electrocution Hazard
Asphyxiation Hazard
Burn Hazard. DO NOT touch hot surfaces.
shock hazard Electrical Shock Hazard
Fire Hazard
Maintain Safe Distance
Lifting Hazard
Read Manufacturer's Instructions
DO NOT Operate in Wet Conditions


Using a generator indoors CAN KILL YOU IN MINUTES. Generator exhaust contains carbon monoxide. This is a poison you cannot see or smell.


NEVER use inside a home or garage, EVEN IF doors and windows are open.


Only use OUTSIDE and far away from windows, doors, and vents.

SAFETY INSTRUCTIONS

CORRECT USAGE
Example location to reduce risk of carbon monoxide poisoning ONLY use outside and downwind, far away from windows, doors and vents. Direct exhaust away from occupied spaces
CORRECT USAGE

INCORRECT USAGE
Do not operate in any of the following locations:
Near any door, window, or vent

  • Garage
  • Basement
  • Crawl Space
  • Living Area
  • Attic
  • Entry Way
  • Porch
  • Mudroom

warning NOTICE
Install battery-powered carbon monoxide detectors or plug-in carbon monoxide detectors with battery back-up in living areas.


Fire and electrocution hazard. DO NOT connect to a building's electrical system unless the generator and transfer switch have been properly installed and the electrical output has been verified by a qualified electrician. The connection must isolate the generator power from utility power and must comply with all applicable laws and electrical codes.


Electrocution hazard. NEVER use the generator in a location that is wet or damp. NEVER expose the generator to rain, snow, water spray, or standing water while in use. Protect the generator from all hazardous weather conditions. Moisture or ice can cause a short circuit or other malfunction in the electrical circuit.

GENERAL SAFETY PRECAUTIONS

  • NEVER use the generator to power medical support equipment.
  • DO NOT operate the generator when you are tired or under the influence of drugs, alcohol, or medication.
  • DO NOT use generator with electrical cords which are worn, frayed, bare, or otherwise damaged.
  • All electrical tools and appliances operated from this generator must be properly grounded by use of a third wire or be double-insulated.
  • When this generator is used to supply a building wiring system the generator must be installed by a qualified electrician and connected to a transfer switch as a separately derived system in accordance with NFPA 70, National Electrical Code.
  • If you begin to feel sick, dizzy, or weak while using the generator, move to fresh air IMMEDIATELY. See a doctor, as you can have carbon monoxide poisoning.
  • Only use OUTSIDE and far away from windows, doors, and vents as recommended by the US Department of Health and Human Services Centers for Disease Control and Prevention. Your specific home and/or wind conditions may require additional distance.
  • While operating and storing, keep at least five feet of clearance on all sides of the generator, including overhead. Allow the generator to cool a minimum of 30 minutes before storage. Heat created by the muffler and exhaust gases could be hot enough to cause serious burns and/or ignite combustible objects.
  • DO NOT touch the muffler or engine. They are very HOT and will cause severe burns. DO NOT put body parts or any flammable or combustible materials in the direct path of the exhaust.
  • ALWAYS remove any tools or other service equipment used during maintenance away from the generator before operating.
  • Avoid skin contact with engine oil or gasoline. Wear protective clothing and equipment. Wash all exposed skin with soap and water.

FUEL SAFETY

  • Store fuel in a container approved for gasoline.
  • DO NOT smoke when filling the generator with gasoline.
  • DO NOT allow the generator's gas tank to overflow when filling.
  • Shut down the engine and allow it to cool for two minutes before adding gasoline or oil to the generator.
  • NEVER remove the fuel cap when the generator is running. Shut off the engine and allow the unit to cool at least two minutes. Remove the fuel cap slowly to release pressure, keep fuel from escaping around the cap, and to avoid the heat from the muffler igniting fuel vapors. Tighten the fuel cap securely after refueling.
  • Wipe spilled fuel from the unit.
  • NEVER attempt to burn off spilled fuel.
  • NEVER overfill the fuel tank. Leave room for fuel to expand. Overfilling the fuel tank can result in a sudden overflow of gasoline and result in spilled gasoline coming in contact with HOT surfaces.
  • Spilled fuel can ignite. If fuel is spilled on the generator, wipe up any spills immediately. Dispose of rag properly. Allow area of spilled fuel to dry before operating the generator.
  • Wear eye protection while refueling.
  • NEVER use gasoline as a cleaning agent.
  • Store any containers containing gasoline or LPG/ propane in a well-ventilated area, away from any combustibles or source of ignition.

GASOLINE AND GASOLINE VAPOR (GAS)


Fire and explosion hazard. Gasoline and LPG/propane are highly explosive and flammable and can cause severe burns or death.

  • In case of a gas fire, DO NOT attempt to extinguish the flame if the fuel tank valve is in the ON position. Introducing an extinguisher to a generator with an open fuel valve could create an explosion hazard.
  • Gas has a distinctive odor, this will help detect potential leaks quickly.
  • Gas vapors can cause a fire if ignited.
  • Gasoline is a skin irritant and needs to be cleaned up immediately if it comes in contact with the skin.

When starting the generator:

  • Make sure that the fuel cap, air filter, spark plug, fuel lines, and exhaust system are properly in place.
  • If you spill any gasoline on the tank, allow it to fully evaporate before operating.
  • Make sure the generator is on a flat surface before operating.

When transporting or servicing the generator:

  • Disconnect the spark boot to prevent accidental starting.

When storing the generator:

  • Store away from sparks, open flames, pilot lights, heat, and other sources of ignition.
  • DO NOT store gas near furnaces, water heaters, or any other appliances that produce heat or have automatic ignitions.

SAFETY LABELS AND DECALS

SAFETY LABELS AND DECALS - Part 1

SAFETY LABELS AND DECALS - Part 2
SAFETY LABELS AND DECALS - Part 3

EZ START INSTRUCTIONS

START

a.
START

SHUT DOWN

b.
SHUT DOWN

COMPONENTS

CONTROL PANEL COMPONENTS

CONTROL PANEL COMPONENTS

  1. Push-Button START/STOP: Push once to automatically start the engine. Push again to stop the engine.
  2. Battery Switch: Turns battery ON and OFF. Must be ON before electric or remote start.
  3. Data Center: Toggle to show voltage, frequency, total hour meter, and run/maintenance timer.
  4. Main Circuit Breaker: The main circuit breaker controls total output of all outlets to protect the generator from overload or short circuit.
  5. 120/240 Volt AC, 30 Amp NEMA 14-30R Twist-Lock Receptacle: Receptacle can supply a maximum of 30 Amps.
  6. 120 Volt AC, 20 Amp Duplex GFCI NEMA 5-20R Receptacles: Receptacles can supply a maximum of 20 Amps.
  7. 20 Amp AC Circuit Breakers: Circuit breakers limits the current that can be delivered through the NEMA 5-20R receptacles to 20 Amps.
  8. Ground Terminal: The ground terminal is used to externally ground the generator.
  9. Smart Switch Outlet: Connects the Westinghouse ST Switch (sold separately) to the control panel.
  10. Battery Charging Port: Used to charge the battery with the included battery charger.
  11. Battery Indicator: Indicates that power is ON. Light will remain illuminated while the unit is ON.

DATA CENTER

Voltage:
Displays current voltage output.
Frequency (Hz):
Displays power output frequency in Hertz.
Lifetime Hours:
Displays the lifetime run hours.
Run Time/Maintenance:
Displays current run time. Resets to zero when shut down. Maintenance reminder displayed when required.

Push the Mode button to cycle through the data display modes.
Mode button

GENERATOR COMPONENTS

GENERATOR COMPONENTS

ASSEMBLY

CARTON CONTENTS


Weight hazard. ALWAYS have assistance when lifting the generator.

  1. Carefully open the carton.
  2. Remove and save the carton contents.
  3. Remove and discard the packing tray.
  4. Unfold the top of the plastic bag enclosing the generator.
  5. Carefully cut the vertical corners of the carton to access the generator.
  6. Recycle or dispose of the packaging materials properly.

CARTON CONTENTS

  • User manual
  • Quick Start Guide
  • Remote start key fob (attached to recoil starter)
  • 1.16 Quart (1.1 Liter) bottle of SAE 10W-30 Oil
  • Battery charger
  • Spark plug socket wrench
  • Oil Funnel
  • Assembly wrench

Wheel and mounting foot components

  • Mounting foot (2)
  • Flange bolt, M8 (4)
  • Wheel (2)
  • Axle pin (2)
  • Washer (2)
  • Cotter pin (2)

If any parts are missing, contact our service team at service@wpowereq.com or call 1-855-944-3571.

INSTALL FEET AND WHEELS

warning NOTICE
Assembling the generator will require lifting the unit on one side. Install the mounting feet and wheel before adding fuel or oil.

  1. Place generator on a flat surface.
  2. Tip the generator on a piece of cardboard or other soft material to protect the frame paint and prevent the generator from sliding.
  3. With the included wrench, install the mounting feet to the frame as shown.
  4. Install the wheels as shown.
    INSTALL FEET AND WHEELS

warning Note: The wheels are only intended for hand transport. The wheels are not suitable for towing the generator either on or off-road.

INITIAL OIL FILL

warning NOTICE
THIS GENERATOR HAS BEEN SHIPPED WITHOUT OIL
. DO NOT attempt to crank or start engine before it has been properly serviced with recommended oil. Failure to add engine oil before starting will result in serious engine damage.

warning NOTICE
Use of 2-stroke/cycle oil or other unapproved oil types can cause severe engine damage that is not covered under warranty.

The included, recommended oil type for typical use is 10W-30 engine oil. If running the generator in extreme temperatures, refer to the following chart.
INITIAL OIL FILL - recommended oil type

  1. On a level surface, remove the oil dipstick.
    On a level surface, remove the oil dipstick.
  2. Using the supplied funnel and oil, add oil into oil filler neck.
    warning Note: As residual oil from the factory may remain in the engine, add the oil incrementally near the end of the bottle to prevent overfilling the engine. See Engine Oil Level Check in the Maintenance section.
  3. Replace the oil dipstick and hand-tighten.

FUEL


Fire and explosion hazard. NEVER use a gasoline container, gasoline tank, propane connector hose, propane tanks, or any other fuel item that is broken, cut, torn or damaged.


Fire and explosion hazard. DO NOT overfill fuel tank. Fill only to the red fill ring located in the in-tank fuel screen filter. Overfilling may cause fuel to spill onto engine causing a fire or explosion hazard.


Fire and explosion hazard. NEVER refuel the generator while the engine is running. ALWAYS turn the engine off and allow the generator to cool for two minutes before refueling.

warning NOTICE

DO NOT use E15 or E85 fuel in this product. Engine or equipment damage caused by stale fuel or the use of unapproved fuels (such as E15 or E85 ethanol blends) is not covered by warranty. Only use unleaded gasoline containing up to 10% ethanol.

FUEL REQUIREMENTS

  • CLEAN, FRESH, unleaded gasoline, 87–93 octane.
  • Up to 10% ethanol (gasohol) is acceptable (where available; non-ethanol fuel is recommended).
  • DO NOT use E85 or E15.
  • DO NOT use a gas oil mix.
  • DO NOT modify the engine to run on alternate fuels.
  • DO NOT fuel indoors.
  • DO NOT create a spark or flame while fueling.

USING FUEL STABILIZER

Adding a fuel stabilizer (not included) extends the usable life of fuel and helps prevent deposits from forming that can clog the fuel system. Follow the manufacturer's instructions for use.

ALWAYS mix the correct amount of fuel stabilizer to gasoline in an approved gasoline container before fueling the generator. Run the generator for five minutes to allow the stabilizer to treat the entire fuel system.

FILLING THE FUEL TANK

  1. Turn the generator OFF and allow to cool for a minimum of two minutes before fueling.
  2. Place the generator on level ground in a well ventilated area.
  3. Clean area around fuel cap and remove the cap slowly.

warning NOTICE
Only fill the tank from an approved gasoline container. Make sure the gasoline container is internally clean and in good condition to prevent fuel system contamination.

  1. Slowly add the recommended fuel. DO NOT overfill. Fill only to the red maximum fill ring on the fuel screen filter visible in the filler neck.
  2. Install the fuel cap.

warning NOTICE
Fuel can damage paint and plastic. Use caution when filling the fuel tank. Damage caused by spilled fuel is not covered under warranty.

warning NOTICE
Clean the fuel screen filter of debris before and after each fueling. Remove the fuel screen filter by slightly compressing it while removing it from the fuel tank.

CONNECT THE BATTERY

A quick-connect battery plug is pre-installed on the battery. Remove the cable tie securing the plugs then push firmly to connect them.

warningNote: The generator is equipped with a battery charging feature. Once the engine is running, a small charge will slowly recharge the battery.

OPERATION

GENERATOR LOCATION

Read and understand all safety information before starting the generator.


Using a generator indoors CAN KILL YOU IN MINUTES. Generator exhaust contains carbon monoxide. This is a poison you cannot see or smell.


NEVER use inside a home or garage, EVEN IF doors and windows are open.


Only use OUTSIDE and far away from windows, doors, and vents.

NEVER operate the generator inside any building, including garages, basements, crawlspaces, sheds, enclosure, or compartment, including the generator compartment of a recreational vehicle.


Electrocution hazard. NEVER use the generator in a location that is wet or damp. NEVER expose the generator to rain, snow, water spray, or standing water while in use. Protect the generator from all hazardous weather conditions. Moisture or ice can cause a short circuit or other malfunction in the electrical circuit. Using a generator or electrical appliance in wet conditions, such as rain or snow, or near a pool or sprinkler system, or when your hands are wet, could result in electrocution


Fire hazard. Only operate the generator on a solid, level surface. Operating the generator on a surface with loose material such as sand or grass clippings can cause debris to be ingested by the generator that could block cooling vents or the air intake system. Allow the generator to cool for 30 minutes before transport or storage.

The generator should be on a flat, level surface at all times (Even while not in operation). The generator must have at least 5 ft. (1.5 m) of clearance from all combustible material.

DO NOT operate the generator in the back of a SUV, camper, trailer, truck bed (regular, flat, or otherwise), under stairs, next to walls or buildings, or in any other location that will not allow for adequate cooling of the generator and/or the muffler. DO NOT contain generators during operation.


Asphyxiation hazard. Place the generator in a wellventilated area. DO NOT place the generator near vents or intakes where exhaust fumes could be drawn into occupied or confined spaces. Carefully consider wind and air currents when positioning the generator.

GROUNDING


Shock hazard. Failure to properly ground the generator can result in electric shock.

warning NOTICE
Only use grounded 3-prong extension cords, tools, and appliances, or double-insulated tools and appliances.

The generator neutral is bonded to the frame. There is a permanent conductor between the generator (stator wire) and the frame. If this generator will be used only with cord and plug equipment connected to the receptacles mounted on the generator, National Electric Code does not require that the unit be grounded. However, other methods of using the generator may require grounding to reduce the risk of shock or electrocution.
Before using the ground terminal, consult a qualified electrician, electrical inspector, or local agency having jurisdiction for local codes or ordinances that apply to the intended use of the generator.

DISCONNECTING THE BONDED NEUTRAL

Removing the bonded neutral disables the GFCI protection from the 5-20R receptacles. The bonded neutral should only be removed under specific circumstances. Consult a qualified electrician to determine if your situation requires disconnecting the bonded neutral.

  1. Remove the alternator cover.
  2. Remove the bonded jumper wire and reinstall the nut.
    DISCONNECTING THE BONDED NEUTRAL - Step 1
  3. Remove the nut securing the neutral ground wire and attach the bonded jumper wire. Reinstall the nut.
    DISCONNECTING THE BONDED NEUTRAL - Step 2
  4. Reinstall the alternator cover.


Apply a new "NEUTRAL UNBONDED" Label over the "NEUTRAL BONDED TO FRAME" label on the front of the control panel.

HIGH ALTITUDE OPERATION

Engine power is reduced the higher you operate above sea level. Output will be reduced approximately 3.5% for every 1000 feet of increased altitude from sea level.
High altitude adjustment is required for operation at altitudes over 5,000 ft. (1524 m). Operation without this adjustment will cause decreased performance, increased fuel consumption, and increased emissions.

warning NOTICE
DO NOT
operate the generator at altitudes below 2,000 ft. (762 m) with the high altitude kit installed. Engine damage may occur

High Altitude Carburetor Kit Part# 518063

REMOTE START


Verify that the area around the generator is clear before remote starting the generator.

The remote start key fob included with the generator should be attached to the recoil handle or control panel. If your unit was shipped without a key fob, contact Westinghouse customer service.

The generator can be started remotely from up to 99 feet (30 meter) using the remote start key fob.

warning Note: As the batteries in the remote start key fob drain, operational distance will decrease.

PAIRING THE REMOTE START

Remote replacement batteries: (2) CR2016

If the remote start key fob is replaced or needs re-paired to the generator, follow this procedure.

  1. Turn the generator battery switch to the ON position. The power indicator light will illuminate.
    PAIRING THE REMOTE START
  2. Push and hold the red Pairing button on the side of the control panel until the START/STOP button illuminates.
  3. Push and hold the STOP button on the key fob until the START/STOP button illumination turns OFF. Release the button. The START/STOP button will illuminate after the button is released.
  4. Push and hold the START button on the key fob until the START/STOP button illumination turns OFF. Release the button. The START/STOP button will illuminate after the button is released.
  5. Push the Pairing button on the side of the control panel until the START/STOP button illumination turns OFF. Release the button.
  6. Turn the generator battery switch to the OFF position. The remote is now paired.

BREAK-IN PERIOD

For proper break-in, DO NOT exceed 50% of the rated running watts (3750 watts) during the first five hours of operation.

Vary the load occasionally to allow stator windings to heat and cool and help seat the piston rings.

BEFORE STARTING THE GENERATOR

Verify that:

  • The generator is placed in an safe, appropriate location.
  • The generator is on a dry, flat, and level surface.
  • The engine is filled with oil.
  • All loads are disconnected.


Fire and explosion hazard. DO NOT move or tip the generator during operation.

STARTING THE ENGINE

  1. Verify that gasoline is in the fuel tank.
  2. Turn the fuel tank valve to the ON position.
  3. Push the battery switch to the ON position.
  4. Choose the starting method:
    1. Remote Start: Push and hold the START button on the remote start key fob for one second.
    2. Push-Button Start: Push and hold the engine START/STOP button for two seconds.
    3. Recoil Start: Manually close the choke if the engine is cold. Firmly grasp and pull the recoil handle slowly until you feel increased resistance, then pull rapidly.
      Recoil Start

warning Note: During Push-Button or Remote Start the engine will automatically set the choke and begin the start sequence. If the engine fails to start, the generator will attempt to start the engine two more times.

STOPPING THE ENGINE

  1. Turn off and unplug all connected electrical loads.

    NEVER start or stop the generator with electrical devices connected.
  2. Let the generator run with no load for several minutes to stabilize internal temperatures of the engine.
  3. Push and hold the START/STOP button for one second or push STOP on the remote start key fob for one second.
    warning Note: Alternately, if the generator is used infrequently, turn the fuel tank valve to the OFF position to limit the residual fuel remaining in the carburetor float bowl. The engine will stop when fuel in the carburetor and fuel line is exhausted.
  4. Push the battery switch to the OFF position.
  5. If operating on LPG, turn the propane tank valve to the fully closed position.

FREQUENCY OF USE

If the generator will be used on an infrequent or intermittent basis (more than one month before next use), refer to the Battery Maintenance and Storage sections of this manual for information regarding battery charging and fuel deterioration.

AC CIRCUIT BREAKERS

The circuit breakers will automatically switch OFF if there is a short circuit or a significant overload of the generator at each receptacle. The main circuit breaker will automatically switch OFF if the combined load of the receptacles exceeds 40 Amps.

If an AC circuit breaker switches OFF automatically, check that the appliance is working correctly and it does not exceed the rated load capacity of the circuit before resetting the AC circuit breaker ON.

Receptacle Circuit Breakers

Main Circuit Breaker

GENERATOR CAPACITY

warning NOTICE
DO NOT
overload the generator's capacity. Exceeding the generator's wattage/amperage capacity can damage the generator and/or electrical devices connected to it.

Make sure the generator can supply enough continuous (running) and surge (starting) watts for the items you will power at the same time.

The total power requirements (Volts x Amps = Watts) of all appliances connected must be considered. Appliance and power tool manufacturers usually list rating information near the model or serial number.

To determine power requirements:

  1. Select the items you will power at the same time.
  2. Total the continuous (running) watts of these items. This is the amount of power the generator must produce to keep the items running. See the wattage reference chart below.
  3. Estimate how many surge (starting) watts you will need. Surge wattage is the short burst of power needed to start electric motor-driven tools or appliances such as a circular saw or refrigerator. Because not all motors start at the same time, total surge watts can be estimated by adding only the item(s) with the highest additional surge watts to the total rated watts from step 2.

Example:

Tool or Appliance Running Watts* Starting Watts*
RV Air Conditioner (11,000 BTU) 1010 1600
TV (Tube Type) 300 0
RV Refrigerator 180 600
Radio 200 0
Light (75 Watts) 300 0
Coffee Maker 600 0
2590 Total
Running Watts*
1600
Highest Starting Watts*
Total Running Watts 2590
Highest Starting Watts + 1600
Total Starting Watts Needed 4190

*Wattages listed are approximate. Verify actual wattage.

POWER MANAGEMENT

To prolong the life of the generator and attached devices, use care when adding electrical loads to the generator. There should be nothing connected to the generator outlets before starting the engine. The correct and safe way to manage generator power is to sequentially add loads as follows:

  1. With nothing connected to the generator, start the engine as described in this manual.
  2. Plug in and turn on the first load, preferably the largest load you have.
  3. Permit the generator output to stabilize (engine runs smoothly and attached device operates properly).
  4. Plug in and turn on the next load.
  5. Again, permit the generator to stabilize.
  6. Repeat steps 4 and 5 for each additional load.

Wattage Reference

Tool or Appliance Estimated Running Watts* Estimated Starting Watts*
Incandescent Lights
(4 Quantity x 75 Watts)
300 0
TV (Tube Type) 300 0
Sump Pump (1/3 hp) 800 1300
Refrigerator or Freezer 700 2200
Well Pump (1/3 hp) 1000 2000
Furnace (1/2 hp) 800 2350
Radio 200 0
Drill (3/8", 4 amps) 440 600
Circular Saw
(Heavy Duty, 7-1/4")
1400 2300
Miter Saw (10") 1800 1800
Table Saw (10") 2000 2000

*Wattages listed are approximate. Verify actual wattage.

EXTENSION CORDS


Asphyxiation hazard. Extension cords running directly into the home increase the risk of carbon monoxide poisoning through any openings. If an extension cord running directly into your home is used to power indoor items, there is a risk of carbon monoxide poisoning to people inside the home. ALWAYS use battery-powered carbon monoxide detector (s) that meet current UL 2034 safety standards when running the generator. Regularly check the detector (s) battery.


Asphyxiation hazard. When operating the generator with extension cords, make sure the generator is located in an open, outdoor area, far away from occupied spaces with exhaust pointed away.


Fire and electrocution hazard. NEVER use worn or damaged extension cords. Damaged or overloaded extension cords could overheat, arc, and burn resulting in death or serious injury.

Before connecting an AC appliance or power cord to the generator:

  • Use grounded 3-prong extension cords, tools, and appliances, or double-insulated tools and appliances.
  • Make sure the tool or appliance is in good working order. Faulty appliances or power cords can create a potential for electric shock.
  • Make sure the electrical rating of the tool or appliance does not exceed the rated power of the generator or the receptacle being used.

EXTENSION CORD SIZING

Only use grounded 3-prong extension cords marked for outdoor use that are rated for the electrical load.

Total Amperage Minimum Gauge, Outdoor Rated
Up to 50 FT (15M) Up to 100 FT (30 M)
Up to 10A
Up to 15A
Up to 20A
Up to 30A
Up to 35A

ST SWITCH

The wGen7500 is compatible with the ST Switch, purchased separately. When utility power is on it will provide power (up to 120V @ 20A) to the appliances plugged into the 5-20R receptacle on the ST Switch. When utility power is lost the ST Switch automatically transfers input power from utility to generator power. When utility power is restored, the ST Switch transfers input power back to utility. Visit www.westinghouseoutdoorpower.com for more information.
ST SWITCH

TRANSPORTING


Weight hazard. ALWAYS have assistance when lifting the generator.

  • Allow the generator to cool a minimum of 30 minutes before transporting.
  • If operating on LPG, turn the propane tank valve to the fully closed position.
  • Disconnect the LPG/propane hose from the generator and propane tank.
  • Replace all protective covers on the generator control panel.
  • Only use the generator's fixed frame to lift the unit or attach any load restraints such as ropes or tie-down straps. DO NOT attempt to lift or secure the generator by holding onto any of its other components.
  • Keep the unit level during transport to minimize the possibility of fuel leakage or, if possible, drain the fuel or run the engine until the fuel tank is empty before transport.
  • The generator wheels are only intended for hand transport. The wheels are not suitable for towing the generator either on or off-road.
  • Use the extendable handle for one-person, hand transport. Only use the handle while the generator is OFF, stationary, and resting on a horizontal surface. DO NOT use the handle to lift the generator entirely off the ground, tow it, or up-end it.


Fire hazard. DO NOT up-end the generator or place it on its side. Fuel or oil can leak and damage to the generator may occur.

MAINTENANCE


Accidental start-up. Disconnect the spark plug boot from the spark plug and disconnect the battery quick-connect plugs when performing maintenance on the generator.

MAINTENANCE SCHEDULE

Regular maintenance will improve performance and extend the service life of the generator. Follow the hourly or calendar intervals, whichever occurs first. More frequent service is required when operating in adverse conditions as noted below.

Before Each Use Check engine oil
After First 25 Hours or First Month Change engine oil
After 50 Hours or Every 6 Months Change engine oil 1
Clean air filter 2
After 100 Hours or Every 6 Months Inspect/clean spark arrestor
Inspect/clean spark plug
Replace fuel filter
Inspect/adjust valve clearance3
After 300 Hours or Every Year Replace spark plug Replace air filter

1 Change oil every month when operating under heavy load or in high temperatures.
2 Clean more often under dirty or dusty conditions. Replace air filter if it cannot be adequately cleaned.
3 Recommend service to be performed by authorized Westinghouse service dealer.

MAINTENANCE REMINDERS

Maintenance reminder codes will be shown on the Data Display based on unit Lifetime Hours. The maintenance codes will be displayed until the unit is turned off. Refer to the Maintenance section for specific procedures.

Maintenance Code Required Maintenace
P25 Change engine oil
P50 Change engine oil, clean air filter
P100 Change engine oil, clean air filter, replace fuel filter

MAINTENANCE REPLACEMENT PARTS

Description Part Number
Air filter 5046
Oil drain plug crush washer 94004
Spark arrestor 6866
Battery, 9.0 AH 511008
Spark plug 97108

AIR FILTER MAINTENANCE


Fire hazard. NEVER use gasoline or other flammable solvents to clean the air filter. Use only household detergent soap to clean the air filter.

The air filter must be cleaned after every 50 hours of use or six months (frequency should be increased if the generator is operated in a dusty environment).

  1. Place the generator on a level surface and allow the engine to cool for several minutes.
  2. Release the top and bottom clips then remove the air filter cover.
    AIR FILTER MAINTENANCE
  3. Remove the air filters. Use compressed air to clean the coarse air filter.
    warning Note: The foam air filter element is oil soaked. Use an appropriate cleaning container.
    warning NOTICE
    Avoid skin contact with engine oil. Wear protective clothing and equipment. Wash all exposed skin with soap and water.
  4. Remove the foam air filter and wash it by submerging the element in a solution of household detergent soap and warm water. Slowly squeeze the foam to thoroughly clean.
    warning NOTICE
    DO NOT
    twist or tear the foam air filter element during cleaning or drying. Only apply slow but firm squeezing action.
  5. Rinse the air filter element by submerging it in fresh water and applying a slow squeezing action. Allow the filter to dry thoroughly.
    warning NOTICE
    DO NOT
    pollute. Follow the guidelines of the EPA or other governmental agencies for proper disposal of hazardous materials. Consult local authorities or reclamation facility.
  6. Dip the foam air filter in clean engine oil then squeeze out all excess oil. The engine will smoke when started if too much oil is left in the filter.
  7. Install the foam air filter in the housing, then the coarse air filter. Install the air cleaner cover and secure with the cover clips.

ENGINE OIL LEVEL CHECK


Avoid skin contact with engine oil. Wear protective clothing and equipment. Wash all exposed skin with soap and water.

warning NOTICE
ALWAYS
use the specified engine oil. Failure to use the specified engine oil can cause accelerated wear and/or shorten the life of the engine.

When using the generator under extreme, dirty, dusty conditions or in extremely hot weather, change the oil more frequently.
Ambient air temperature will affect engine oil performance. Change the type of engine oil used based on weather conditions.
ENGINE OIL LEVEL CHECK - Step 1

Check the engine oil level before each use or every 8 hours of operation.

  1. Place the generator on a level surface and allow the engine to cool for several minutes.
  2. With a damp rag, clean around the oil dipstick then remove the dipstick.
    ENGINE OIL LEVEL CHECK - Step 2
  3. Wipe the dipstick clean, then insert it into the oil filler neck without screwing it in. Remove the dipstick and verify that the oil level is within safe operating range between the low (L) and high (H) marks on the dipstick.
  4. If low, add recommended engine oil incrementally and recheck until the level is between the L and H marks on the dipstick. DO NOT overfill. If over the full mark on the dipstick, drain the oil to reduce the oil level to the full mark.
  5. Replace the oil dipstick and hand-tighten.

ENGINE OIL CHANGE

When using the generator under extreme, dirty, dusty conditions or in extremely hot weather, change the oil more frequently. Change the oil while the engine is still warm from operation.

  1. Place the generator on a level surface and allow the engine to cool for several minutes.
  2. With a damp rag, clean around the oil dipstick. Remove the dipstick and wipe clean.
  3. Place an oil pan (or suitable container) under the oil drain bolt.
  4. Using a 10mm wrench, remove the oil drain bolt and allow the oil the to drain.
    ENGINE OIL LEVEL CHECK - Step 3
  5. Install the oil drain bolt and tighten securely.
    warning Note: A new oil drain plug crush washer is recommended at each oil change.
  6. Slowly pour oil into the oil filler neck until oil the level is between the L and H marks on the dipstick. Stop frequently to check the oil level. DO NOT overfill.
    Maximum oil capacity: 1.16 Quart (1.1 Liter) 7 Install the oil dipstick and hand-tighten.
  7. Install the oil dipstick and hand-tighten.

warning NOTICE
DO NOT
pollute. Follow the guidelines of the EPA or other governmental agencies for proper disposal of hazardous materials. Consult local authorities or reclamation facility.

SPARK PLUG MAINTENANCE

Inspect and clean the spark plug after every 100 hours of use or six months. Replace the spark plug after 300 hours of use or every year.

  1. Place the generator on a level surface and allow the engine to cool.
  2. Remove the spark plug boot by firmly pulling the spark boot directly away from the engine.
  3. Clean the area around the spark plug.
  4. Remove the spark plug with the included spark plug socket wrench.
    warning NOTICE
    NEVER
    apply any side load or move the spark plug laterally when removing the spark plug
  5. Inspect the spark plug. Replace if electrodes are pitted, burned, or the insulator is cracked. Only use a recommended replacement plug.
  6. Measure the spark plug electrode gap with a wire-type feeler gauge. If necessary, correct the gap by carefully bending the side electrode.
    Spark plug gap: 0.024 – 0.032 in. (0.60 – 0.80 mm)
    Spark plug gap
  7. Carefully install the spark plug finger tight, then tighten as additional 3/8 to 1/2 turn with the spark plug wrench.
  8. Attach the spark plug boot.

SPARK ARRESTOR SERVICE

Allow the muffler to cool completely before servicing the spark arrestor. Check and clean the spark arrestor after every 100 hours of use or six months. Failure to clean the spark arrestor will result in degraded engine performance.

  1. Place the generator on a level surface.
  2. Remove the cover screws and the muffler cover. Use a screw driver to remove the spark arrestor.

  3. Carefully remove the carbon deposits from the spark arrestor screen with a wire brush. The spark arrestor must be free of breaks and tears. Replace the spark arrestor if damaged.
  4. Reinstall the spark arrestor and muffler cover.

BATTERY MAINTENANCE

The battery shipped with the generator has been fully charged. A battery may lose some charge when not in use for prolonged periods of time.

warning Note: Once started, the generator will charge the battery after 30–60 minutes of use.

The included trickle charger can remain connected and will maintain the battery for an indefinite period of time. A red light on the charger indicates charging in progress. A green light indicates charging complete. Charge in a dry location.

  1. Plug the charger into the battery charging port on the control panel.
  2. Plug the wall receptacle end of the battery charger into a 120 Volt AC wall outlet.

BATTERY REPLACEMENT


Burn hazard. The battery contains sulfuric acid (electrolyte) which is highly corrosive and poisonous. Wear protective clothing and eye protection when working near the battery. Keep children away from the battery.


Battery posts, terminals contain lead and lead compounds. Wash hands after handling.

  1. Loosen and remove the bolt on the battery hold-down plate and swing the plate out.
  2. Disconnect the quick-connect plugs and remove the battery from the unit.
  3. Disconnect the quick-disconnect cable leads from the battery.
  4. On the replacement battery, connect the white (-) quickconnect cable to the battery negative terminal. Slide the rubber boot over the connection hardware.
  5. Connect the red (+) quick-connect cable to the battery positive terminal. Slide the rubber boot over the connection hardware.
  6. Install the battery into the generator. Reinstall the battery hold-down plate and tighten the bolt.
  7. Connect the quick-connect plug.
    warning NOTICE
    Dispose of the used battery properly according to the guidelines established by your local or state government.

STORAGE

Proper storage preparation is required for trouble-free operation and generator longevity.

warning NOTICE
Gasoline stored for as little as 30 days can deteriorate, causing gum, varnish, and corrosive buildup in fuel lines, fuel passages, and the engine. This corrosive buildup restricts the flow of fuel, which can prevent the engine from starting after a prolonged storage period. The use of fuel stabilizer significantly increases the storage life of gasoline. Full-time use of fuel stabilizer is recommended.
Follow the manufacturer's instructions for use.

STORAGE TIME RECOMMENDED PROCEDURE
Less than 1 month No service required.
2 to 6 months Fill with fresh gasoline and add gasoline stabilizer. Drain the carburetor float bowl.
6 months or longer Drain the fuel tank and carburetor float bowl.

SHORT TERM STORAGE

  • Allow the generator to cool a minimum of 30 minutes before storage.
  • If operating on LPG, turn the propane tank valve to the fully closed position and disconnect the LPG/propane hose from the generator and propane tank.
  • Replace all protective covers on the generator control panel.
  • Wipe the generator with a moist cloth. Clean any debris from the muffler cooling vents.
  • Store the generator in a well-ventilated, dry location away from sparks, open flames, pilot lights, heat, and other sources of ignition such as areas with a sparkproducing electric motor or where power tools are operated.
  • DO NOT store the generator, gasoline, or propane tanks near furnaces, water heaters, or any other appliances that produce heat or have automatic ignitions.
  • With the engine and exhaust system cool and all surfaces dry, cover the generator to keep out dust. DO NOT use a plastic sheet as a dust cover. Non-porous materials trap moisture and promote rust and corrosion.

LONG TERM STORAGE

Even properly stabilized fuel can leave residue and cause corrosion if left long term. If storing the generator for two to six months, drain the float bowl to prevent gum and varnish buildup in the carburetor.

DRAINING THE FLOAT BOWL

  1. Turn the fuel tank valve to the OFF position.
  2. Locate the drain screw on the bottom of the carburetor float bowl.
    DRAINING THE FLOAT BOWL
  3. Place an appropriate gasoline container under the drain screw to catch the drained fuel.
  4. Loosen the float bowl drain screw and allow the fuel to drain. Tighten the float bowl drain screw.

DRAINING THE FUEL TANK

If storing the generator for longer than six months, drain the fuel tank to prevent fuel separation, deterioration, and deposits in the fuel system.

  1. Unscrew the fuel tank cap. Remove the fuel screen filter by slightly compressing it while removing it from the tank.
  2. Using a commercially available gasoline hand pump (not included), siphon the gasoline from the fuel tank into an approved gasoline container. DO NOT use an electric pump.
  3. Reinstall the fuel screen filter and the fuel tank cap.
  4. Start the generator and allow it to run until the generator engine stops.
  5. Push the battery switch to the OFF position.
  6. Disconnect the battery quick-connect plugs.
  7. Remove the spark plug.
  8. Put a teaspoon of engine oil into the cylinder and pull the recoil handle until resistance is felt. At this position the piston is coming up on its compression stroke and both valves are closed. Storing the engine in this position will help prevent internal corrosion. Return the recoil handle gently.
  9. Reinstall the spark plug. Leave the spark plug boot disconnected to prevent accidental starting.

VALVE CLEARANCE

warning NOTICE
Checking and adjusting valve clearance must be done when the engine is cold.

  1. Remove the rocker arm cover and carefully remove the gasket. If the gasket is torn or damaged, it must be replaced.
  2. Remove the spark plug so the engine can be rotated more easily.
  3. Rotate the engine to top dead center (TDC) by pulling the recoil handle slowly. Looking through the spark plug hole, the piston should be at the top (both valves are closed).
  4. Both the rocker arms should be loose at TDC on the compression stroke. If they are not, rotate the engine 360°.
  5. Insert a feeler gauge between the rocker arm and the valve stem to measure valve clearance.
Intake Valve Exhaust Valve
Valve Clearance 0.0031 – 0.0047 in
(0.08 – 0.12 mm)
0.0051 – 0.0067 in
(0.13 – 0.17 mm)
Torque 8-12 N•m 8-12 N•m
  1. If an adjustment is necessary, hold the rocker arm pivot and loosen the pivot adjusting nut.
  2. Turn the rocker arm pivot to obtain the specified clearance. Hold the rocker arm pivot and re-tighten the pivot adjusting nut to the specified torque.
    Torque: 106 inch-pound (12 N•m)
  3. Perform this procedure for the other valve.
  4. Install the gasket, rocker arm cover, and spark plug.

TROUBLESHOOTING

PROBLEM POSSIBLE CAUSE CORRECTION
Engine will not start Battery switch in the OFF position. Turn battery switch to the ON position.
Out of fuel. Refuel.
Bad fuel, generator stored without treating or draining gasoline, or refueled with bad gasoline. Drain the fuel tank. Refuel with fresh gasoline.
Dirty air filter. Clean the air filter.
Low engine oil level stopped generator. If low oil LED illuminated, turn battery switch to the OFF position. Add engine oil.
Spark plug wet with fuel (flooded engine). Wait five minutes. Turn battery switch to the OFF position. Pull recoil handle rapidly several times. If the generator does not start, remove spark plug and dry.
Spark plug faulty, fouled, or improperly gapped. Gap or replace the spark plug. Reinstall.
Fuel filter restricted, fuel system malfunction, fuel pump failure, ignition malfunction, valves stuck, etc. Contact Westinghouse customer service tollfree at
1 (855) 944-3571.
Battery drained. Use the recoil handle to start the generator.
Charge the battery.
Choke partially open or closed due to weak or disconnected battery. Manually set the choke. See Maintenance section.
Engine starts, then shuts down Out of fuel. Refuel.
Incorrect engine oil level. Check engine oil level.
Dirty air filter. Clean the air filter.
Contaminated fuel. Drain the fuel tank. Refuel with fresh gasoline.
Defective low oil level switch. Contact Westinghouse customer service tollfree at
1 (855) 944-3571.
Engine lacks power Air filter restricted. Clean or replace air filter.
Bad fuel, generator stored without treating or draining gasoline, or refueled with bad gasoline. Drain the fuel tank. Refuel with fresh gasoline.
Fuel filter restricted, fuel system malfunction, fuel pump failure, ignition malfunction, valves stuck, etc. Contact Westinghouse customer service tollfree at
1 (855) 944-3571.
Engine runs rough or bogs when load applied Dirty air filter. Clean the air filter.
Generator overloaded. Unplug some devices.
Faulty power tool or appliance. Replace or repair tool or appliance. Stop and restart the engine.
Fuel filter restricted, fuel system malfunction, fuel pump failure, ignition malfunction, valves stuck, etc. Contact Westinghouse customer service tollfree at
1 (855) 944-3571.
No power at AC receptacles OUTPUT READY LED is OFF and OVERLOAD LED is ON. Check AC load. Stop and restart engine.
Check the air inlet. Stop and restart the engine.
AC circuit breaker/s tripped. Check AC loads and reset circuit breaker/s.
Faulty power tool or appliance. Replace or repair tool or appliance. Stop and restart the engine.
Faulty generator. Contact Westinghouse customer service tollfree at
1 (855) 944-3571.

EXPLODED VIEWS AND PARTS LISTS

EXPLODED VIEW A

EXPLODED VIEW A

NO. PART# DESCRIPTION
1 CRANKCASE ASSEMBLY
1.1 260218 CRANKCASE
1.2 93002 AXLE BEARING
1.3 93512 CRANKCASE OIL SEAL
1.4 93516 GOVERNOR OIL SEAL
1.5 263901 GOVERNOR SHAFT
1.6 96806 SHAFT GASKET
1.7 263902 RETAINING CLIP
1.8 265102 OIL SENSOR ASSEMBLY
1.9 91329 BOLT M6X16
1.10 269901 CABLE BLOCK
1.11 245104 LOW OIL SENSOR
2 260319 CRANKSHAFT
3 260301 BALANCE SHAFT
4 CRANKCASE COVER ASSEMBLY
4.1 93002 AXLE BEARING
4.2 93512 CRANKCASE OIL SEAL
4.3 240904 CRANKCASE LOCATING PIN
4.4 260111 CRANKCASE COVER
4.5 93015 AXLE BEARING
4.6 264301 GOVERNOR GEAR ASSEMBLY
4.7 96072 CRANKCASE GASKET
4.8 91349 BOLT M8X40
4.9 265604- 295 DIPSTICK
5 ALTERNATOR ASSEMBLY
5.1 266101 VALVE LIFTER
5.2 272003 CAMSHAFT ASSEMBLY
5.3 261901 PUSH ROD
6 GOVERNOR ASSEMBLY
6.1 264001 SPEED REGULATING ARM
6.2 91325 BOLT M6X12
6.3 264404 SPEED CONTROLLER
6.4 262701 THROTTLE LEVER
6.5 264201 SPRING C
6.6 264101 SPRING B
7 PISTON & PISTON RING ASSEMBLY
7.1 261205 PISTON
7.2 261604 PISTON RING ASSEMBLY
7.3 261503 CONNECTING ROD ASSEMBLY
7.4 265501 PISTON PIN
7.5 261301 PISTON PIN RING
8 97108 SPARK PULG
9 CYLINDER HEAD ASSEMBLY
9.1 271005 CYLINDER HEAD
9.2 271702 INTAKE VALVE
9.3 275902 INTAKE VALVE
9.4 261807 EXHAUST VALVE
9.5 93513 VALVE SEAL
9.6 266002 VALVE SPRING
9.7 260802 VALVE LOCK CLAMP
9.8 261805 AIR INLET SPRING SEAT
9.9 262201 VALVE RETAINER ASSEMBLY
9.10 262101 ROCKER ARM
9.11 261806 TOP CAP
9.12 91016 AIR INLET STUD BOLT
9.13 91007 AIR EXHAUST STUD BOLT
9.14 96083 EXHAUST SEAL WASHER
9.15 95207 MUFFLER CONNECTING PIPE
9.16 94206 SPRING WASHER
9.17 90011 NUT M8
9.18 91818 ROCKER ARM TIGHTENING ASSEMBLY
9.19 260901 CYLINDER HEAD LOCATING PIN
9.20 96089 CYLINDER HEAD GASKET
9.21 91321 BOLT M10X80
9.22 270501 WIND-LEAD-COVER
9.23 91325 BOLT M6X12
9.24 96078 INTAKE SEALING WASHER
9.25 262301 CARBURETOR CONNECTION BLOCK
10 CYLINDER HEAD COVER ASSEMBLY
10.1 261104 CYLINDER HEAD COVER
10.2 91819 FASTENING BOLT
10.3 95606 BREATHER TUBE
11 CARBURETOR ASSEMBLY
11.1 262852 CARBURETOR
11.2 95713L FUEL HOSE
11.3 94403 FUEL HOSE CLAMP
11.4 94401 FUEL HOSE SLEEVE
11.5 260801 CABLE CLIP
11.6 249904 STEPPER MOTOR
11.7 92007 CROSS SCREW STUD M4*8
11.8 249905 STEPPER MOTOR DRIVE SHAFT
11.9 244202 SPRING
11.10 269909 BRACKET
12 AIR FILTER ASSEMBLY
12.1 90016 NUT M6
12.2 262908-052 AIR CLEANER ASSEMBLY
13 IGNITION COIL ASSEMBLY
13.1 97518 IGNITION COIL
13.2 91331 BOLT M6X25
14 FLYWHEEL ASSEMBLY
14.1 260407 FLYWHEEL
14.2 264601 IMPELLER
14.3 264501 STARTER PULLEY
14.4 90004 FLYWHEEL NUT
15 RECOIL STARTER ASSEMBLY
15.1 91325 BOLT M6X12
15.2 264738- 221B STARTER ASSEMBLY
15.3 5910-221 RECOIL STARTER
15.4 5943 HANDLE
16 STARTER MOTOR ASSEMBLY
16.1 97415 STARTING MOTOR
16.2 91348 BOLT M8*35
17 91817 OIL DRAIN BOLT
18 94004 OIL DRAIN BOLT CRUSH WASHER
19 96075 HEADCOVER GASKET
20 96081 CARBURATOR GASKET
21 5046 AIR FILTER
22 96086 AIR FILTER GASKET

EXPLODED VIEW B

EXPLODED VIEW B

NO. PART# DESCRIPTION
1 FRAME ASSEMBLY
1.1 774010-116 FRAME
1.2 531314 ISOLATOR
1.3 90013 NUT M10
1.4 90018 NUT M8
1.5 90011 NUT M8
1.6 91327 BOLT M6X12
1.7 91343 BOLT M8X16
1.8 544307 GROUND WIRE
1.9 94009 TOOTH WASHER
1.10 96120 WASHER
1.11 530606-116 FUEL TANK BRACKET
2 CONTROL PANEL ASSEMBLY
2.1 91327 BOLT M6X12
2.2 714305 PANEL ASSEMBLY
2.3 536002 PUSH BUTTON SWITCH
2.4 6393 INDICATOR LIGHT
2.5 6502 ROCKER SWITCH
2.6 6387 2.5MM CHARGING SOCKET
2.7 6041 DATA CENTER
2.8 6488 ST SWITCH
2.9 6523 BREAKER 30/2P/31A/1.25/CSA
2.10 6386 GROUND BOLT ASSEMBLY
2.11 6385 L14-30R RECEPTACLE 30A/125V/250V
L14-30R/UL
2.12 6848 WATERPROOF CAP
2.13 6275 GFCI SOCKET
2.14 6845 WATERPROOF CAP
2.15 6439-20 THERMAL PROTECTOR 20A/CSA
2.16 96120 WASHER
3 FOOT BRACKET ASSEMBLY
3.1 91343 BOLT M8X16
3.2 525608-116 FOOT BRACKET ASSEMBLY
3.3 531115 FOOT BRACKET SHOCK ABSORBER
3.4 91333 BOLT M6X28
3.5 90023 NUT M6
4 ENGINE ASSEMBLY
4.1 540601 AIR FILTER BRACKET
4.2 1148420
120030
ENGINE ASSEMBLY
4.3 549603 DUST BOARD
4.4 91322 BOLT M5X12
4.5 90016 NUT M6
4.6 539602 CRANKCASE COVER
5 CARBON CANISTER ASSEMBLY
5.1 95123 CARBON CANISTER AND FUEL TANK
CONNECTING PIPE
5.2 91327 BOLT M6X12
5.3 94423 FUEL HOSE CLAMP
5.4 94408 FUEL HOSE CLAMP
5.5 543601L CARBON CANISTER
5.6 95124 CONNECTING PIPE
5.7 94402 FUEL HOSE CLAMP
6 HANDLE ASSEMBLY
6.1 527603 HANDLE PLUG
6.2 527612 BOLT M10
6.3 526620-116 HANDLE
6.4 528607 HANDLE COVER
7 WHEEL ASSEMBLY
7.1 94207 FLAT WASHER
7.2 523646 WHEEL
7.3 524619 AXLE PIN
7.4 548302 COTTER PIN
8 FUEL TANK ASSEMBLY
8.1 700375L-116 FUEL TANK ASSEMBLY
8.2 6861 FUEL GAUGE
8.3 91460 BOLT M6X25
8.4 518202 FUEL SWITCH
8.5 94403 FUEL LINE CLAMP
9 MUFFLER ASSEMBLY
9.1 520305 MUFFLER BRACKET
9.2 91343 BOLT M8X16
9.3 96002 MUFFLER CONNECTING PIPE GASKET
9.4 94206 SPRING WASHER
9.5 705944 MUFFLER
9.6 91347 BOLT M8X30
10 60140041 ALTERNATOR ASSEMBLY
10.1 757551 ALTERNATOR
10.2 599019 CARBON BRUSH
10.3 6560 TERMINAL ASSEMBLY
10.4 532301 BRACKET
10.5 96813 GASKET
10.6 91717 BOLT M10X1.25X275
10.7 91614 BOLT M6X190
10.8 91322 BOLT M5X12
10.9 534813 AVR
10.10 533302-221 ALTERNATOR COVER
10.11 91512 BOLT M5X230
10.12 90009 NUT M5
10.13 91323 BOLT M5X16
10.14 544610 GROUNDING WIRE
10.15 532303-052 BRACKET
10.16 94204 SPRING WASHER
11 BATTERY ASSEMBLY
11.1 91327 BOLT M6X12
11.2 542614-116 BATTERY HOLD DOWN
11.3 512058 BATTERY WIRING ASSEMBLY
11.4 91325 BOLT M6X12
12 519215 FUEL TANK CAP
13 6866 SPARK ARRESTER
14 518801 FILTER
15 511008 BATTERY
16 99504 FUNNEL
17 99010 SPARK PLUG WRENCH
18 99546 OIL BOTTLE
19 511076 CHARGER
20 99025 WRENCH

SCHEMATICS

SCHEMATICS

If you have questions or need assistance, please call customer service at 855-944-3571.

Documents / Resources

References

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Download Westinghouse WGen7500 - Portable Generator Manual