Mitsubishi Electric MELSEC-F FX3U-232ADP-MB Installation Manual page 2

Advertisement

FX
(D, DS, DSS) Series PLC
3UC
Communication port channels are automatically allocated. The communication
special adapter closer to the main unit is ch1.
(ch2)
(ch1)
Analog
Analog
FX
-
Analog
Analog
FX
-
3U
3U
special
special
232ADP
special
special
232ADP
Main unit
adapter
adapter
-MB
adapter
adapter
-MB
3. Installation
For installation/uninstallation details, refer to the respective PLC User's manual
Hardware Edition.
INSTALLATION
PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before
attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
INSTALLATION
PRECAUTIONS
• Use the product within the generic environment specifications described in
PLC main unit manual (Hardware Edition).
Never use the product in areas with excessive dust, oily smoke, conductive
dusts, corrosive gas (salt air, Cl
, H
S, SO
, or NO
), flammable gas, vibration
2
2
2
2
or impacts, or expose it to high temperature, condensation, or rain and wind.
If the product is used in such conditions, electric shock, fire, malfunctions,
deterioration or damage may occur.
• When drilling screw holes or wiring, make sure that cutting and wiring debris
do not enter the ventilation slits of the PLC.
Failure to do so may cause fire, equipment failures or malfunctions.
• Do not touch the conductive parts of the product directly.
Doing so may cause device failures or malfunctions.
• Connect special adapter securely to their designated connectors.
Loose connections may cause malfunctions.
3.1 Connection to the PLC
This section describes the connection method to the PLC (FX
Series PLC is
3U
used for the following example).
For installation method to other PLCs, refer to the respective PLC User's manual
Hardware Edition.
Procedure
1) Turn off the power.
Disconnect all the cables connected to the PLC main unit and special adapter.
Dismount the main unit and special adapter mounted on DIN rail or mounted
directly using screws.
2) Install an expansion board to the main unit.
For installation of expansion board, refer to the following manual:
→ FX
Series User's Manual - Hardware Edition
3U
3) Remove the special adapter connector cover
on the expansion board (Right fig.A).
In case of connecting this product to another
special
adapter,
please
replace
the
4)
'expansion board' in the above description
with a 'special adapter' and perform the
procedure as indicated.
B
3)
4) Slide the special adapter slide lock (Right
fig.B) of the main unit.
In case of connecting this product to another
special adapter, please replace the 'main
A
unit' in the above description with a 'special
adapter' and perform the procedure as
indicated. (Please replace the following
procedures similarly.)
5) Connect the
B
special adapter
(Right fig.C) to
C
the main unit as
6)
shown on the
right.
6) Slide back the
special adapter
5)
slide lock (Right
fig.B) of the main
unit to fix the
5)
special adapter
(Right fig.C).
5)
Connection precautions
Connect all the high-speed I/O special adapters before connecting other
special adapters when they are used in combination.
Do not connect a high-speed I/O special adapter on the left side of a
communication or analog special adapter.
4. Wiring
For wiring details, refer to the following manual.
→ FX Series User's Manual - Data Communication Edition
→ FX
/FX
/FX
/FX
3S
3G
3GC
3
U
- MODBUS Serial Communication Edition
WIRING
PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting
installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
WIRING
PRECAUTIONS
• When drilling screw holes or wiring, make sure cutting or wire debris does not
enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to observe the following precautions in order to prevent any damage to
the machinery or accidents due to abnormal data written to the PLC under the
influence of noise:
- Do not bundle the main circuit line together with or lay it close to the main
circuit, high-voltage line or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place.
As a guideline, lay the control line at least 100mm (3.94") or more away from
the main circuit or high-voltage lines.
5. Specification
STARTUP AND
MAINTENANCE
PRECAUTIONS
• Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
* For repair, contact your local Mitsubishi Electric representative.
• Do not drop the product or exert strong impact to it.
Doing so may cause damage.
DISPOSAL
PRECAUTIONS
• Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
TRANSPORTATION AND
STORAGE PRECAUTIONS
• The product is a precision instrument. During transportation, avoid impacts larger
than those specified in the general specifications by using dedicated packaging
boxes and shock-absorbing palettes. Failure to do so may cause failures in the
product. After transportation, verify operation of the product and check for damage
of the mounting part, etc.
5.1 Applicable PLC
Model name
Applicability
FX
3S
Series PLC
Ver. 1.00 or later for all communication functions
Ver. 1.30 or later for MODBUS communication
FX
Series PLC
Ver. 1.00 or later for all communication functions except
3G
MODBUS
FX
3GC
Series PLC
Ver. 1.40 or later for all communication functions
4)
Ver. 2.40 or later for MODBUS communication
FX
Series PLC
Ver. 2.20 or later for all communication functions except
3U
MODBUS
Ver. 2.40 or later for MODBUS communication
FX
Series PLC
Ver. 1.00 or later for all communication functions except
3UC
B
MODBUS
The version number can be checked by monitoring D8001/D8101, as well the last three
digits indicate the version number.
5.2 General Specifications
Items other than the following are equivalent to the those of the PLC main unit.
For general specifications, refer to the respective PLC User's manual Hardware Edition.
Item
Specification
6)
Dielectric withstand
500 V AC, one minute
voltage
B e t w ee n t e rm in a l b l oc k a nd
5 MΩ or higher by 500 V
ground terminal of PLC main unit
Insulation resistance
DC insulation resistance
tester
B
5.3 Power Supply Specification
Item
/FX
Series User's Manual
3UC
30 mA
Current consumption
5 V DC power is supplied internally from the main unit.
5.4 Performance Specification
Item
Transmission
Conforming to RS-232C
standard
Type of isolation
Photocoupler isolation
Transmission
15 m (49' 2") or less
distance
Connection method
9-pin D-Sub connector (male)
Number of occupied
0 point (This number is not related to the maximum number
I/O points
of input/output points of the PLC.)
Communication
Full-duplex
method
Computer link, and Non-protocol Items other than the
following are equivalent to the those of the PLC main unit.
For general specifications, refer to the respective PLC
User's manual Hardware Edition.:
300/600/1200/2400/4800/9600/19200/38400
Programming communication:
Baud rate
9600/19200/38400/57600/115200 bps
Remote maintenance: 9600 bps
MODBUS communication
300/600/1200/2400/4800/9600/19200/38400
115200
Computer link (dedicated protocol: format 1/format 4),
Communication
Non-protocol, Programming communication, Remote
format
maintenance, and MODBUS communication
LED display:
Power: green, RD: red, SD: red
LED color
*1 Applicable for FX
/FX
Series PLC Ver. 2.41 or later and FX
3U
3UC
Series PLC.
*2 When you set the baud rate to 38400 bps or more in a FX
PLC, please set D8411 (D8431) to be 3 ms or more. When D8411 (D8431) is set
at less than 3 ms, it may not be able to communicate normally.
*3 Applicable for products manufactured in July, 2012 or later (manufacturer's serial
number: 127**** or later). The year and month of production of the special
adapter can be checked from the manufacturer's serial number "S/N" indicated
on the label.
For manufacturer's serial number, refer to the following manual.
→ FX
/FX
3S
6. 「电器电子产品有害物质限制使用标识要求」的表示方式
Note: This symbol mark is for China only.
含有有害6物质的名称,含有量,含有部品
 本产品中所含有的有害6物质的名称, 含有量, 含有部品如下表所示。
产品中有害物质的名称及含量
部件名称
(Pb)
外壳
可编程
控制器
印刷基板
×
本表格依据SJ/T 11364的规定编制。
○:表示该有害物质在该部件所有均质材料中的含量均在GB/T 26572规
定的限量要求以下。
×:表示该有害物质至少在该部件的某一均质材料中的含量超出GB/T
26572规定的限量要求。
Specification
Specification
*1
bps
*2
:
*3
*3
/57600
/
*3
bps
/FX
/FX
3S
3G
3GC
/FX
/FX
Series
3S
3G
3GC
/FX
/FX
/FX
SERIES USER'S MANUAL
3G
3GC
3U
3UC
- MODBUS Serial Communication Edition
This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
Warranty
Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to:
(1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
有害物质
(2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products.
(3) Special damages and secondary damages whether foreseeable or not, compensation for
多溴
六价铬
多溴联苯
accidents, and compensation for damages to products other than Mitsubishi products.
二苯醚
(Hg)
(Cd)
(Cr(VI))
(PBB)
(4) Replacement by the user, maintenance of on-site equipment, start-up test run
(PBDE)
and other tasks.
This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.
This product has been manufactured under strict quality control. However
when installing the product where major accidents or losses could occur if the
product fails, install appropriate backup or failsafe functions in the system.
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
For safe use

Advertisement