[ III Specifications ]
Model
Power source
Cooling capacity
(Nominal)
Power input
Current input
Heating capacity
(Nominal)
Power input
Current input
Reheat capacity
(Nominal)
External finish
External dimension H x W x D
Net weight
Heat exchanger
FAN
Type x Quantity
External*8
static press
Motor type
Motor output
Driving mechanism
Airflow rate
Sound pressure level*8
(Static pressure : Low-Mid-High)
(measured in anechoic room)
Insulation material
Air filter
Protection device
Refrigerant control device
Liquid (Main)
Diameter of
Gas (Main)
refrigerant
pipe (O.D.)
Liquid (Reheat)
Gas (Reheat)
Diameter of drain pipe
Note :
1.Standard capacities are the maximum capacities that are obtained in the following conditions;
Indoor
Outdoor
Pipe length
Height difference
2.This value shows the data per unit.
3.Sound pressure level is the data that was obtained in anechoic room by the following conditions;
The measuring point is 4.9feet (1.5m) from the bottom of the unit that has 6.6feet (2m) outlet duct and 3.3feet (1m) intake duct.
4.When combining the drain pipes, ensure that collected pipes are 3-15/16inch(10cm) lower than the unit body's drain port.
5.Install BC controller in a location where noise (refrigerant noise etc.) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the BC controller at least 16.4feet(5m) away from any indoor units.)
6.When connecting the indoor unit to the BC controller, the optional twinning pipe shall be installed.
(Refer to Figure1 and Table1)
7.The choice of indoor unit operation mode is limited to auto mode.
8.Figures in parentheses indicate factory settings.
[Figure1]
Reheat Main
Twinning pipe
(CMY-R160-J)
BC controller
HWE13100
BTU / h
kW
kW
A
BTU / h
kW
kW
A
BTU / h
kW
in.
mm
lbs (kg)
Cross fin (Aluminium fin and copper tube)
in.WG
Pa
in.WG
Pa
kW
cfm
m3 / min
L / s
dB <A>
dB <A>
Polyethylene foam, Polyurethane foam, Polystyrene foam
in. (mm)
in. (mm)
in. (mm)
in. (mm)
in. (mm)
cooling conditions
87°FDB/80°FWB(30.5°CDB/26.7°CWB)
87°FDB(30.5°CDB)
24.6ft.(7.5m)
0ft.(0m)
[Table1]
Indoor unit
Fan motor
Number of connection pipe of BC
Outdoor
model
Intake air
P120
Twinning pipe
(CMY-R320C-J)
Twinning pipe
(CMY-R160-J)
PEFY-AF1200CFMR-E
1-phase 208/230V 60Hz
112,000
32.8
0.66/0.78
3.19/3.45
61,400
18
0.66/0.78
3.19/3.45
24,200
7.1
Galvanized
18-9/16 x 49-1/4 x 55-1/8
470 x 1,250 x 1,400
305 (138)
Sirocco fan x 2
(0.28)-(0.48)-0.80 (208V)
(70)-(120)-200
(0.52)-(0.72)-0.96 (230V)
(130)-(180)-240
Single phase induction motor
0.62/0.74
Direct-driven
1,200
34
566
(36)-(40)-43 (208V)
(39)-(42)-45 (230V)
Field supply
Fuse
LEV
3/8 (9.52) Brazed
7/8 (22.2) Brazed
3/8 (9.52) Brazed
7/8 (22.2) Brazed
O.D. 1-1/4(32) x 2
heating conditions
32°FDB(0°CDB)
32°FDB/28°FWB(0°CDB/-2°CWB)
24.6ft.(7.5m)
0ft.(0m)
Main Reheat
4
2
- 5 -