Mitsubishi Electric CITY MULTI PEFY-AF1200CFM-E Technical & Service Manual page 23

Table of Contents

Advertisement

[ VIII Troubleshooting ]
(4) Linear expansion valve
Disconnect the connector, and measure the resistance between terminals with a tester.
Refer to the next page for details.
CN60
(F)
1
(E)
2
(D)
3
M
(C)
4
(B)
5
LEV
(A)
6
(A)
Brown
(B)
Red
(C)
Blue
1) Summary of linear expansion valve (LEV) operation
The LEV is operated by a stepping motor, which operates by receiving a pulse signal from the indoor control board.
The LEV position changes in response to the pulse signal.
Indoor control board and LEV connection
(J)
(C)
4
(A)
M
6
(E)
2
5
1
3
(F)
(B)
(D)
(A)
Brown
(B)
Red
(C)
Blue
(D)
Orange
(E)
Yellow
Pulse signal output and valve operation
Phase
number
1
ø1
ON
ø2
ON
ø3
OFF
ø4
OFF
The output pulse changes in the following order:
When the valve closes 1 -> 2 -> 3 -> 4 -> 1
When the valve opens 4 -> 3 -> 2 -> 1 -> 4
When the valve position remains the same, all output signals will be OFF.
If any output signal is missing or if the signal remains ON, the motor vibrates and makes clicking noise.
HWE13100
Normal
1-5
2-6
White-Red
Yellow-Brown
200
(D)
Orange
(E)
Yellow
(F)
White
(F)
White
(G)
Control board
(H)
Connection (CN60,CN7V)
(I)
Drive circuit
(J)
Linear expansion valve
Output pulse
2
3
OFF
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
ON
3-5
4-6
Orange-Red
Blue-Brown
10%
(A)
(B)
(C)
(D)
(E)
(F)
(H)
4
ON
ON
- 19 -
Abnormal
Open or short
(G)
12VDC
6
5
(I)
4
3
2
1