13

EASY MAINTENANCE FUNCTION

13-1. SMOOTH MAINTENANCE
13-1-1. <PAR-3xMAA ("x" represents 0 or later)>
Maintenance data, such as the indoor/outdoor unit's heat exchanger temperature and compressor operation current can be
displayed with "Smooth maintenance".
This cannot be executed during test operation.
Depending on the combination with the outdoor unit, this may not be supported by some models.
Reduces maintenance work drastically.
Enables you to check operation data of the indoor and outdoor units by remote controller.
Furthermore, use of maintenance stable-operation control that fixes the operating frequency, allows smooth inspection, even for
inverter models.
Smooth Mainte-
nance Function
Smooth maintenance
Ref.address
Sub cool
OU TH4 temp.
OU TH6 temp.
OU TH7 temp.
Return:
Page
Easy maintenance information (unit)
Compressor
Outdoor unit
Accumulated operating
Heat exchanger
1
4
time (o10 hours)
temperature (:)
Number of ON/OFF
Discharge
2
5
times (o10 times)
temperature (:)
Operating
Outside air
3
6
current (A)
temperature (:)
* The filter operating time is the time that has elapsed since the filter was reset.
Select "Service" from the Main menu, and press the
Select "Check" with the F1 or F2 button, and press the
Select "Smooth maintenance" with the F1 or F2 button, and press the
button.
Set each item.
Select the item to be changed with the F1 or F2 button.
Select the required setting with the F3 or F4 button.
■ <Ref.address>setting [ 0 ]−[ 15 ]
■ <Stable mode>setting [ Cool ] / [ Heat ] / [ Normal ]
Press the
button, Fixed operation will start.
Stable mode will take approx. 20 minutes.
OCH679
Discharge temperature 60°C
Cool
Indoor unit
Intake air
7
temperature (:)
Heat exchanger
8
temperature (:)
Filter operating
9
time* (Hours)
button.
Conventional inspection work
●Outdoor unit ●
Measure
Remove the
the intake air
service panel.
temperature.
Measure the discharge
Measure the outside
temperature.
air temperature.
1
button.
2
92
●Indoor unit ●
Check menu
Error history
Refrigerant volume check
Refrigerant leak check
Smooth maintenance
Request code
Service menu:
Cursor
F1
F2
F3
F4
Smooth maintenance
Ref.address
Stable mode
Cool
/ Heat/ Normal
Begin:
−Address+
Cursor
Smooth maintenance
Ref.address
Stable mode
Cool
/ Heat/ Normal
Stabilization→Collecting
Exit:
Continue to the next page