Use the WEIGH-IN method for adding initial refrigerant charge, and then use SUBCOOLING method for for verifying
refrigerant charge.
WEIGH-IN
CHARGING METHOD
64ºF (17.7ºC) and Below
Adjust amount for variation in
line set length and liquid line
Amount specified
diameter using table below.
on nameplate
+
Liquid Line
Set Diameter
5/16"
3/8"
1/2"
SUBCOOLING
1. THE DIAGNOSTIC SCREEN ON THE THERMOSTAT OR OUTDOOR CONTROL 7-SEGMENT DISPLAY WILL SHOW INDOOR AND
OUTDOOR MOTOR CFMS OR RPMS.
2. MEASURE OUTDOOR AMBIENT TEMPERATURE.
3. CONNECT GAUGE SET.
4. CHECK LIQUID AND VAPOR LINE PRESSURES. COMPARE PRESSURES WITH COOLING MODE NORMAL OPERATING
PRESSURES IN THE APPLICABLE CHARGING STICKER, NORMAL OPERATING PRESSURES AT MAXIMUM CAPACITY.
NOTE
DIFFERENCES MAY MEAN IMPROPER CHARGE OR OTHER SYSTEM PROBLEM.
5. SET THERMOSTAT FOR HEAT/COOL DEMAND, DEPENDING ON MODE BEING USED:
USE
USING COOLING MODE
COOLING
MODE
SUBCOOLING VALUES (MAXIMUM / 100% CAPACITY) IN APPLICABLE CHARGING STICKER ARE BASED ON 70 TO
80°F (21-27°C) INDOOR RETURN AIR TEMPERATURE; IF NECESSARY, OPERATE HEATING TO REACH THAT
60ºF
TEMPERATURE RANGE; THEN SET THE INITIAL COOLING DEMAND AT MAXIMUM CAPACITY. THE PREFERRED METHOD IS
(15ºC)
TO USE THE "CHARGE MODE" JUMPER ON THE OUTDOOR CONTROL. SEE CHARGE MODE JUMPER SECTION ON PAGE 80.
USE
WHEN PRESSURES HAVE STABILIZED, CONTINUE WITH STEP 6.
HEATING
MODE
6. READ THE LIQUID LINE TEMPERATURE; RECORD IN THE LIQº SPACE.
7. READ THE LIQUID LINE PRESSURE; THEN FIND ITS CORRESPONDING TEMPERATURE IN THE TEMPERATURE/ PRESSURE
8. SUBTRACT LIQº TEMPERATURE FROM SATº TEMPERATURE TO DETERMINE SUBCOOLING; RECORD IT IN SCº SPACE.
9. COMPARE SCº RESULTS WITH APPLICABLE CHARGING STICKER, BEING SURE TO NOTE ANY ADDITIONAL CHARGE FOR
10. IF SUBCOOLING VALUE IS GREATER THAN SHOWN IN APPLICABLE CHARGING STICKER FOR THE APPLICABLE UNIT,
SATº
11. IF REFRIGERANT IS ADDED OR REMOVED, REPEAT STEPS 6 THROUGH 10 TO VERIFY CHARGE.
LIQº –
12. DISCONNECT GAUGE SET AND RE-INSTALL BOTH THE LIQUID AND SUCTION SERVICE VALVE CAPS.
SCº
=
Figure 51. Using HFC-410A Subcooling Method - High Speed (High Capacity)
31-5000746 Rev. 0
Total charge
=
HFC-410A
(ounces per foot)
0.40
0.60
1.00
Figure 50. Using HFC-410A Weigh-In Method
CHARGING METHOD
-
THE REFERENCE TABLE IS A GENERAL GUIDE. EXPECT MINOR PRESSURE VARIATIONS. SIGNIFICANT
— WHEN THE OUTDOOR AMBIENT TEMPERATURE IS 60°F (15°C) AND ABOVE. TARGET
CHART LISTED IN THE APPLICABLE CHARGING STICKER AND RECORD IT IN THE SATº SPACE.
LINE SET AND/OR MATCH-UP.
REMOVE REFRIGERANT; IF LESS THAN SHOWN, ADD REFRIGERANT.
NOTE - Insulate liquid line when it is routed through areas where
the surrounding ambient temperature could become higher than
the temperature of the liquid line or when pressure drop is equal
to or greater than 20 psig.
NOTE - The nameplate is shown for illustration purposes only. Go to
actual nameplate on outdoor unit for charge information.
Charging Formula for Liquid Line Charge Adjustments
Example
Factory charge for 3/8" is 0.60 oz/ft x 15 = 9.0 ounces.
(All charging MUST be performed while system is operating
either at maximum speed or 100% demand.)
Page 93
.