4. Installation chart annex

4. Installation chart annex
<Installation example of safety measures>
* The alarm shall warn audibly and visibly such as both a loud buzzer and flashing light.
(1) Machinery room installation (Continuous ventilation)
Supply
Supply
HBC controller
HBC controller
HBC controller
(2) Small room installation (No safety measures)
Unoccupied space not designated a machinery room
HBC controller
HBC controller
HBC controller
Height ≥ 1.8m
Height ≥ 1.8m
Height ≥ 1.8m
(4) Small room installation (Alarm + Shut-off valves)
Unoccupied space not designated a machinery room
Shut-off
Shut-off
Shut-off
valve
valve
valve
HBC controller
HBC controller
HBC controller
Height ≥ 1.8m
Height ≥ 1.8m
Height ≥ 1.8m
Leak detector
Leak detector
+ alarm
+ alarm
(6) Small room installation (Shut-off valves + Ventilation)
Unoccupied space not designated a machinery room
Supply
Supply
Shut-off
Shut-off
Shut-off
valve
valve
valve
HBC controller
HBC controller
HBC controller
Height ≥ 1.8m
Height ≥ 1.8m
Height ≥ 1.8m
Leak detector
Leak detector
MEES18K044
Machinery room
(Continuously)
(Continuously)
(Continuously)
Mechanical ventilation
Mechanical ventilation
Mechanical ventilation
Exhaust
Exhaust
Exhaust
Concentration
check
Supervised location
Supervised location
Supervised location
Alarm (Hospital etc)
Alarm (Hospital etc)
Alarm (Hospital etc)
Concentration
check
Concentration
check
(Continuously)
(Continuously)
(Continuously)
Mechanical ventilation
Mechanical ventilation
Mechanical ventilation
Exhaust
Exhaust
Exhaust
Machinery room
Supply
Supply
(3) Small room installation (Alarm)
Unoccupied space not designated a machinery room
HBC controller
HBC controller
HBC controller
Height ≥ 1.8m
Height ≥ 1.8m
Height ≥ 1.8m
Leak detector
Leak detector
+ alarm
+ alarm
(5) Installation on ceiling (Alarm + Ventilation)
Unoccupied space not designated a machinery room
Supply
Supply
HBC controller
HBC controller
HBC controller
Height ≥ 1.8m
Height ≥ 1.8m
Height ≥ 1.8m
Leak detector
Leak detector
+ alarm
+ alarm
(7) Small room installation (Shut-off valves)
Unoccupied space not designated a machinery room
Shut-off
Shut-off
Shut-off
valve
valve
valve
HBC controller
HBC controller
HBC controller
Height ≥ 1.8m
Height ≥ 1.8m
Height ≥ 1.8m
Leak detector
Leak detector
SAFETY HANDLING FOR R32
(Continuously)
(Continuously)
(Continuously)
Mechanical ventilation
Mechanical ventilation
Mechanical ventilation
Exhaust
Exhaust
Exhaust
The mechanical
ventilation mustn't
be installed in the
higher postition in
the room.
Supervised location
Supervised location
Supervised location
Alarm (Hospital etc)
Alarm (Hospital etc)
Alarm (Hospital etc)
Concentration
check
Supervised location
Supervised location
Supervised location
Alarm (Hospital etc)
Alarm (Hospital etc)
Alarm (Hospital etc)
Concentration
check
(Continuously)
(Continuously)
(Continuously)
Mechanical ventilation
Mechanical ventilation
Mechanical ventilation
Exhaust
Exhaust
Exhaust
Concentration
check