Triggering Fire Verification; Alarm Verification; Starting Time To Investigate - Bosch AVENAR panel 8000 Manual

Hide thumbs Also See for AVENAR panel 8000:
Table of Contents

Advertisement

Available languages

Available languages

AVENAR panel 8000 | AVENAR panel 2000 |
AVENAR keypad 8000
4
1.
2.
The control units are reset to the initial state.
In the Controlo field on the status bar, the number of control elements is reduced by the
number of reset elements.
To reset transmission devices, carry out the same steps, but select Disp. de transmissão in
step 1.
10.7

Triggering fire verification

10.7.1

Alarm verification

The transmission of the alarm is delayed. The alarm message must be checked to ensure it is
correct in the place where the detector generating the alarm is located.
An internal buzzer sounds on the panel. The signaling devices (e.g. sirens) and transmission
device to the fire department are not activated.
The time for checking the fire alarm is called the time to investigate. The duration of this time
can be different for every logical zone. The time to investigate is started if the fire alarm is
confirmed on the panel within the time to acknowledge.
Cuidado!
If another fire alarm is reported during the time to investigate, all alarm messages are
!
transmitted to the fire department. The time to investigate is canceled.
If a real fire alarm is detected during the on-site inspection, the alarm must be forwarded to
the fire department; see Triggering alarm manually, página 44 . Alternatively, a manual call
point can be triggered at the location.
If it is a false alarm, the triggering detector can be reset or bypassed; see resetting alarm
message or bypassing detectors.
Cuidado!
All alarm and fault messages from bypassed detectors are no longer displayed.
!
10.7.2

Starting time to investigate

Cuidado!
Se outro alarme for acionado durante o tempo de verificação (alarme externo), o tempo de
!
verificação será suspenso até que os alarmes de incêndio em fila sejam zerados.
Se houver a possibilidade de testar, serão exibidos os seguintes intervalos de tempo. Os
contadores contam até zero:
Bosch Sicherheitssysteme GmbH
Select the signaling device.
Only the activated signaling devices are displayed.
Select one or more list fields.
The list field is marked.
Select Reset.
Tempo para reconhecer O alarme deve ser confirmado dentro do intervalo de tempo
especificado.
Tempo para investigar O alarme deve ser verificado dentro do intervalo de tempo
especificado. Este tempo pode ser especificado de forma diferente para cada zona lógica
ou detector.
Manual do utilizador
Fire alarm | pt-BR
2023-08 | 8.0 | F.01U.378.877
43