Fujitsu AirStage AJY040LCLAH Installation Manual page 16

Table of Contents

Advertisement

(Forbidden)
31
(Factory setting)
(Forbidden)
34
(Factory setting)
Capacity priority
Off (quiet priority)
setting (in low
On (capacity priority)
noise mode)
40
If the cooling/heating performance becomes insuffi cient when the low noise mode is set,
it is possible to set "capacity priority" that automatically cancels the low noise mode (once
performance is restored, the mode will automatically return to the low noise mode).
Off (Normal)
Low noise mode
setting
41
On (Low noise mode)
Low noise mode
Level 1
operation level
Level 2
setting
42
Level1: The operating sound lowers from the rated value
Level2: The operating sound lowers from the Level1
(Forbidden)
60
(Factory setting)
(Forbidden)
61
(Factory setting)
Setting number (x00)
Setting number (x01)
Electricity meter
······
No. setting 1
Setting number (x98)
70
Setting number (x99)
Set the ones digit and tens digit of the No. of the electricity meter connected to
CN135.
Points to note on common No. 70 and 71
If the electricity meter No. is set to "0" or "201-299", the pulse entered into CN135
will be disabled.
Setting number (0xx)
Electricity meter
Setting number (1xx)
No. setting 2
71
Setting number (2xx)
Set the hundreds digit of the No. of the electricity meter connected to CN135.
Setting number (xx00)
Setting number (xx01)
Electricity meter
······
pulse setting 1
Setting number (xx98)
72
Setting number (xx99)
Set the ones digit and tens digit of the No. of the electricity meter pulse setting
connected to CN135.
Points to note on common No 72 and 73
If the electricity meter pulse is set to "0", the pulse entered into CN135 will be
disabled.
Setting number (00xx)
Setting number (01xx)
Electricity meter
······
pulse setting 2
73
Setting number (98xx)
Setting number (99xx)
Set the hundreds digit and thousands digit of the electricity meter pulse setting
connected to CN135.
(Forbidden)
90
(Factory setting)
(1) Turn on the power of the outdoor unit and enter standby mode.
• When system is normal
POWER/MODE lamp lights up. (ERROR lamp is off.)
POWER/MODE lamp:
ON
7 segment display:
turn off
MODE/EXIT button
Initially, when the power is ON, "-- --" will be displayed in the "7 segment display" until "9.1.
Indoor unit connection check" is fi nished.
En-15
3
1
0
0
3
4
0
0
0
0
4
0
0
1
0
0
4
1
0
1
0
0
4
2
0
1
6
0
0
0
6
1
0
0
0
0
0
1
7
0
···
···
9
8
9
9
0
0
7
1
0
1
0
2
0
0
0
1
7
2
···
···
9
8
9
9
0
0
0
1
7
3
···
···
9
8
9
9
9
0
0
0
ERROR lamp: OFF
POWER
ERROR
MODE
LED101
LED102
(GREEN)
(RED)
LED105
LED104
MODE
SELECT
ENTER
/EXIT
SW107
SW108
SW109
SELECT button
ENTER button
(2) Setting method
1: FUNCTION Setting
First 2 digits
Last 2 digits
MODE/EXIT
SELECT
ENTER
2: Setting the
fi rst 2 digits
SELECT
Every press of the
"SELECT" button will
change the setting
number for the fi rst 2
digits.
SELECT
MODE/EXIT
EXIT: Press the "MODE/EXIT" button to cancel the setting mode.
7 segment LED indicator
(LED105, LED104)
(Flashing)
(When [F3] to [F9] are displayed, continue to press
the "SELECT" button until [F2] is displayed.)
3: Setting the last 2 digits
Continue to press the "SELECT" button
until the desired number appears at the
last 2 digits.
ENTER
MODE/EXIT
SELECT
SELECT
SELECT
SELECT
ENTER
Setting is complete when the lamp lights up
Press "ENTER" button to return to "2. Setting
the first 2 digits" (If there is no operation for
5 seconds after the setting, the indicator will
return to "2: Setting the first 2 digits".)
ENTER
MODE/EXIT
SELECT
(Continue to press the
"SELECT" button until the
desired number appears at
the last 2 digits.)
ENTER
Setting is complete when the lamp lights up
Press "ENTER" button to return to "2. Setting the
fi rst 2 digits" (If there is no operation for 5 seconds
after the setting, the indicator will return to
"2: Setting the fi rst 2 digits".)
SELECT
SELECT

Advertisement

Table of Contents
loading

This manual is also suitable for:

Airstage ajy045lclahAirstage ajy054lclah

Table of Contents