Fujitsu AR G45LMLA Series Design & Technical Manual page 29

Hide thumbs Also See for AR G45LMLA Series:
Table of Contents

Advertisement

(6) Repeat steps 2 to 5 to perform additional settings. Press the SET TEMP. buttons (
more than 5 seconds to cancel the function setting mode. In addition, the function setting mode will be automatically canceled after 1
minute if no operation is performed.
(7) After completing the FUNCTION SETTING, be sure to turn off the power and turn it on again.
• After turning off the power, wait 30 seconds or more before turning on it again. The Function Setting will not become active
unless the power is turned off then on again.
CONTENTS OF FUNCTION SETTING
• Follow the instructions in the Local Setup Procedure, which is supplied with the remote control, in accordance with the installed
condition.
After the power is turned on, perform the Function Setting on the remote control.
• The settings may be selected between the following two: Function Number or Setting Value.
• Settings will not be changed if invalid numbers or setting values are selected.
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
11)
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the
room.
If the indication is not required, select "No indication" (03).
Setting Description
Standard (2500 hours)
Long interval (4400 hours)
Short interval (1250 hours)
No indication
2) Static pressure
Select the appropriate static pressure according to the installation conditions.
Setting Description
Normal
High static pressure 1
High static pressure 2
High static pressure 3
3) Room temperature cotrol for cooling
Depending on the installed environment, correction of the room temperature sensor may be required.
Select the appropriate control setting according to the installed environment.
Setting Description
Standard
Slightly lower control
Lower control
Higher control
!
CAUTION
Filter sign
Static pressure
Room temperature cotrol for cooling
Room temperature cotrol for heating
Auto restart
Indoor room temperature sensor switching
Cool air prevention
Remote controller custom code
External input control
Room temperature sensor switching (Aux.)
Indoor unit fan control for energy saving for cooling
(  . . .Factory setting)
Function Number
Setting Value
11
(  . . .Factory setting)
Function Number
Setting Value
21
(  . . .Factory setting)
Function Number
Setting Value
30
- (01 - 26) -
) (
) and FAN button simultaneously again for
00
01
02
03
00
01
02
03
00
01
02
03

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ao g45letl series