Preparations Before Installation - Daikin VRV FXDQ20A2VEB Installation Manual

System inverter air conditioners
Hide thumbs Also See for VRV FXDQ20A2VEB:
Table of Contents

Advertisement

4.

PREPARATIONS BEFORE INSTALLATION

(1) Confirm the positional relationship between the unit
and suspension bolts. (Refer to Fig. 2)
• Install the inspection opening on the control box side where
maintenance and inspection of the control box and drain
pump are easy. Install the inspection opening also in the
lower part of the unit.
620
500
Suspension
bolt pitch
Air outlet
Drain pump
SERVICE SPACE
Model
15-20-25-32 type
40-50 type
63 type
(2) Make sure the range of the unit's external static pres-
sure is not exceeded.
(See the technical documentation for the range of the
external static pressure setting.)
4
(length : mm)
Air inlet
Control box
450×450
(Inspection
opening size)
Ceiling
620
Allow view
Inspection door
Fig. 2
(Ceiling opening)
(length: mm)
A
750
950
1150
1140
(3) Open the installation hole. (Pre-set ceilings)
• Once the installation hole is opened in the ceiling where
the unit is to be installed, pass refrigerant piping, drain
piping, transmission wiring, and remote controller wiring
(It is not necessary if using a wireless remote controller)
to the unit's piping and wiring holes.
See "6. REFRIGERANT PIPING WORK", "7. DRAIN
PIPING WORK", and "10. WIRING EXAMPLE".
• After opening the ceiling hole, make sure ceiling is level if
needed. It might be necessary to reinforce the ceiling
frame to prevent shaking.
Consult an architect or carpenter for details.
(4) Install the suspension bolts.
(Use W3/8 to M10 suspension bolts.)
Use a hole-in-anchor for existing ceilings, and a sunken
insert, sunken anchor or other part to be procured in the
field to reinforce the ceiling to bearing the weight of the unit
for new ceiling. (Refer to Fig. 3)
Note: All the above parts are field supplied.
(5) In case of bottom suction
(1) Remove the chamber lid. (7 locations)
(2) Reattached the removed chamber lid in the orientation
shown in Fig. 4. (7 locations)
(3) Attach the air filter (accessory) in the manner shown in
the diagram.
The four holes which cannot be covered by the air filter
should be covered with commercially available tape.
(1)
Air discharge
B
740
940
(2)
Air discharge
Ceiling slab
Anchor bolt
Long nut or turn-buckle
Suspension bolt
Indoor unit
Fig. 3
Air inlet
Chamber lid
Chamber lid
Air inlet
Fig. 4