10. Electrical characteristics
Model name
Voltage
Power
supply
Frequency
Max operating current *1
Starting current
Circuit breaker current
Power cable
Wiring
spec. *2
Connection
cable *3
*1: Maximum current is the total current of the indoor unit and the outdoor unit.
*2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate de-
vices complied to the regional standard.
*3: Limit voltage drop to less than 2%. Increase conductor size if voltage drop is 2% or more.
mm
Cross-sectional area
mm
Limited wiring length
- 45 -
AOYG24KBTB
V
Hz
A
A
A
2
2
m
230 ~
50
13.6
9.7
20
2.5
1.5
31
10. Electrical characteristics