Toshiba RAV-GM561UT-E Service Manual page 96

Hide thumbs Also See for RAV-GM561UT-E:
Table of Contents

Advertisement

No. Part name
1. Detachment
Float
switch
1) Carry out works of item 1 of
assembly
to 7).
2) Remove the fixing screw and then remove the float
switch assembly. (DIA 4 × 25, 1 pc.)
2. Attachment
1) Mount the float switch assembly as before with the
fixing screw.
NOTE :
When mounting the float switch assembly, match
hole of the float switch assembly with projection of
the drain pan.
2) Mount the bell mouth as before.
(DIA 4 × 10, 4 pcs, three claws)
3) Following to works of item 2 of
to 7), attach the parts as before.
Drain pan
1. Detachment
1) Carry out works of item 1 of
panel) item 1 of
box) and works from 2) to 7).
2) Remove the fixing screws a to remove the drain pan.
(DIA 4 ×10, 2 pcs.)
3) Remove two screws c fixing the holding plate and
loosen two screws b on the side of the hanging hook.
2. Attachment
1) Fix parts as before in order of drain cap → drain pan
→ bell mouth → wire box assembly.
NOTE :
For inserting the drain pan, perform the work while
directing the holding plate outward since the
holding plate interrupts its work if it directs to inside
of the body.
2) Following to works of item 2 of
to 7), attach parts as before.
Procedure
, (removing the drain cap), item 1 of
(removing the bell mouth and the electric parts
and works from 1)
and works from 2)
, (removing the ceiling
and works from 2)
– 96 –
Remarks
Float switch assembly
Fixed screw (DIA 4×25)
Hole of float switch assembly
Drain pan projection
Wire box
a
c
Holding plate
b
Turn

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rav-gm561ut-e trRav-gm801ut-eRav-gm801ut-e trRav-gm1101ut-eRav-gm1101ut-e trRav-gm1401ut-e ... Show all

Table of Contents