Quick Start Guide
6 

Trim the transmitter

Devices are calibrated by the factory. Once installed, it is
recommended to perform a zero trim on the sensor to eliminate
error due to mounting position or static pressure effects.
This can be done by performing a zero trim via:
LOI – see
Class 2 master – see
settings
6.1 
Zero trim via Class 2 Master
Procedure
1. Place the transducer block into Out of Service (OOS) mode.
2. Apply zero pressure to device and allow to stabilize.
3. Go to Basic Setup > Calibration and set the lower calibration
point to 0.0.
4. Place the transducer block to AUTO mode.
22
Table 5-1
and
Figure 5-1
Zero trim via Class 2 Master