Trim the transmitter
Devices are calibrated by the factory. Once installed, it is
recommended to perform a zero trim on the sensor to eliminate
error due to mounting position or static pressure effects.
This can be done by performing a zero trim via:
•
LOI – see
•
Class 2 master – see
settings
6.1
Zero trim via Class 2 Master
Procedure
1. Place the transducer block into Out of Service (OOS) mode.
2. Apply zero pressure to device and allow to stabilize.
3. Go to Basic Setup > Calibration and set the lower calibration
point to 0.0.
4. Place the transducer block to AUTO mode.