Flaring Procedure - LG LSN181HSV5 Installation Manual

Standard wall-mounted indoor unit
Table of Contents

Advertisement

INSTALLATION

Flaring Procedure

One of the main causes of refrigerant leaks is a defective connection. For LG HVAC systems, the installer needs to know how perform flared
connections successfully.
• During installation, it is imperative to keep the piping system free of contaminants and debris such as copper burrs, slag, or carbon dust.
Do not use kinked pipe caused by excessive bending in one specific area on its length.
Flaring Procedure
state, or federal standards.
1. Cut the pipe to length.
• Measure the distance between the indoor unit and the outdoor unit.
• Cut the pipes a little longer than measured distance.
2A. Remove the burrs.
• Completely remove all burrs from pipe ends.
• When removing burrs, point the end of the copper pipe down to
avoid introducing foreign materials in the pipe.
2B. Slide the flare nut onto the copper tube.
3. Flaring the pipe end.
• Use the proper size flaring tool to finish flared connections as
shown.
• ALWAYS create a 45° flare when working with R410A.
4. Carefully inspect the flared pipe end.
• Compare the geometry with the figure to the right
• If the flare is defective, cut it off and re-do procedure.
• If flare looks good, blow the pipe clean with dry nitrogen.
Dimensions of the Flare.
90°
"A"
R=0.4 – 0.8
28
Flared Connection Dimensions / Tightening Torque.
Pipe Size (in. O.D.)
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Copper
1.
tube
Pipe
2A.
Reamer
Point
down
3.
Bar
Copper pipe
4.
Smooth
Even Length
Outside Diameter (mm)
1/4
6.35
9.52
3/8
1/2
12.7
15.88
5/8
19.05
3/4
F
MULTI
F
MULTI
Slanted Uneven Rough
90°
2B.
Flare nut
Copper
tube
Handle
Bar
Yoke
Cone
Red arrow
Clamp handle
Inside is shiny with no scratches
Incorrect Flare
Cracked
Slanted
Surface
Damaged
"A" Dimension (mm [in.])
~ 9.1 (11/32 - 23/64)
~ 13.2 (1/2 - 33/64)
~ 16.6 (41/64 - 21/32)
~ 19.7 (49/64 - 25/32)
-
MAX
Uneven
Thickness

Advertisement