Check Pressure Switch; Checklist - Bryant D Series Installation, Start-Up, And Operating Instructions Manual

Deluxe 4-way multipoise fixed-capacity direct-vent condensing gas furnace
Table of Contents

Advertisement

2. Remove main furnace door and disconnect inducer motor
lead wires from wire harness.
3. Turn on 115-v power to furnace.
4. Set thermostat to call for heat and wait 1 minute. When
pressure switch is functioning properly, hot surface ignitor
should NOT glow, and control center diagnostic light
flashes a Status Code 31. If hot surface ignitor glows when
inducer motor is disconnected, shut furnace down immedi-
ately. Determine reason pressure switch did not function
properly and correct condition.
5. Turn off 115-v power to furnace.
6. Reconnect inducer motor leads, reinstall main furnace door,
and turn on 115-v power supply.
1. Put away tools and instruments. Clean up debris.
2. Verify manual reset switch has continuity.
3. Verify that blower and control access doors are properly
installed.
4. Cycle test furnace with room thermostat.
5. Check operation of accessories per manufacturer's instruc-
tions.
6. Review User's Guide with owner.
7. Leave literature packet near furnace.