TERMINALS

Control Circuit Terminals

Terminal Description
Symbol
L
Power Supply
H
O
O2
Frequency Setting
OI
AM
Monitor Output
AMI
FM
Monitor Output
P24
Power Supply
CM1
Run
FW
Command
1
2
3
4
Functions
5
Contact
6
Input
7
8
Common
PLC
Terminal
11
12
13
Open
14
Collector
State
15
Output
CM2
Analog
Sensor
TH
Input
AL0
Relay
State/
AL1
Output
Alarm
AL2
Terminal Arrangement
H
O2
L
O
OI
13
Name
Common Terminal for Analog
Common terminal for H, O, O2, OI, AM, and AMI. Do not ground.
Power Source
Power Source for Frequency
Power supply for frequency command input
Setting
Maximum frequency is attained at DC 10V in DC 0-10V range. Set the voltage at A014 to
Frequency Command Terminal
command maximum frequency below DC 10V.
Frequency Command Extra
O2 signal is added to the frequency command of O or OI in DC 0-±10V range. By
Terminal
changing configuration, frequency command can be input also at O2 terminal.
Maximum frequency is attained at DC 20mA in DC 4-20mA range.
Frequency Command Terminal
When the intelligent terminal configured as AT is on, OI signal is enabled.
Analog Output Monitor (Voltage)
Selection of one function from:
Output frequency, output current, torque, output voltage, input power, electronic thermal
load ratio, and LAD frequency.
Analog Output Monitor (Current)
[DC0-10V output (PWM output)] Selection of one function from: Output frequency, output
current, torque, output voltage, input power, electronic thermal load ratio, and LAD
Digital Monitor (Voltage)
frequency.
[Digital pulse output (Pulse voltage DC 0/10V)] Outputs the value of output frequency as
digital pulse (duty 50%)
Internal power supply for input terminals. In the case of source type logic, common
Power Terminal for Interface
terminal for contact input terminals.
Common terminal for P24, TH, and FM. In the case of sink type logic, common terminal for
Common Terminal for Interface
contact input terminals. Do not ground.
The motor runs forward when FW terminal is ON,
Forward Command Input
and stops when FW is OFF.
Assign 8 functions to terminals.
Intelligent Input Terminals
(Refer to the standard specifications for the functions.)
Common Terminal for
Select sink or source logic with the short-circuit bar on the control terminals.
Intelligent Input Terminals,
Sink logic: Short P24 to PLC / Source logic: Short CM1 to PLC.
Common Terminal for
When applying external power source, remove the short-circuit bar and connect PLC
External Power Supply for
terminal to the external device.
PLCs, etc.
Assign 5 functions to open collector outputs.
When the alarm code is selected at C062, terminal 11-13 or 11-14 are reserved for error
codes of inverter trip.
Intelligent Output Terminals
(Refer to the standard specifications for the functions.)
Both sink and source logic are always applicable between each terminal and CM1.
Common Terminal for
Common terminal for intelligent output terminal 11-15.
Intelligent Output Terminals
The inverter trips when the external thermistor detects abnormal temperature.
Common terminal is CM1.
[Recommended thermistor characteristics]
Thermistor Input Terminals
Allowable rated power: 100mW or over.
Impedance in the case of abnormal temperature: 3kΩ
Note: Thermal protection level can be set between 0 and 9999Ω.
In default setting, an alarm is activated when inverter output is turned off by a protective
Alarm Output Terminals
function.
AM
FM
TH
FW
AM1
P24
PLC
CM1
Screw diameter:M3
Explanation of Terminals
8
CM1
5
3
7
6
4
2
Terminal Width:6.4mm
DC 10V, 20mA max.
Input impedance: 10kΩ, Allowable
input voltage range: DC -0.3-+12V
Input impedance:10kΩ, Allowable
input voltage range: DC 0-±12V
Input impedance: 100Ω, Allowable
input voltage range: DC 0-24mA
DC 0-10V, 2mA max.
DC 4-20mA, 250Ω max.
Digital output frequency
range: 0-3.6kHz, 1.2mA max.
DC 24V, 100mA max.
[Input ON condition]
Voltage between each terminal
and PLC: DC 18V min.
[Input OFF condition]
Voltage between each terminal
and PLC: DC 3V max.
Input impedance between each
terminal and PLC: 4.7Ω
Allowable maximum voltage
between each terminal and
PLC: DC 27V
Decrease in voltage between
each terminal and CM2:
4V max. during ON
Allowable maximum voltage: DC 27V
Allowable maximum current: 50mA
Allowable input voltage range
[ Input Circuit ]
Thermistor
Maximum capacity of relays
AL1-AL0:
AC 250V, 2A(R load)/0.2A(L load)
DC 30V, 8A(R load)/0.6A(L load)
AL2-AL0:
AC 250V, 1A(R load)/0.2A(L load)
DC 30V, 1A(R load)/0.2A(L load)
Minimum capacity of relays
AL1-AL0, AL2-AL0:
AC100V, 10mA DC5V, 100mA
1
14
13
11
AL1
15
CM2
12
AL0 AL2
Ratings
-
-
DC0 - 8V
DC8V
10kΩ
TH
1kΩ
CM1