Space and Location Requirements

For PTN models.
The most important consideration which must be taken into account
when deciding upon the location of air-cooled equipment is the provision
for a supply of ambient air to the condensing unit. Ignoring this essential
requirement will result in higher condensing pressure and contribute
to poor operation or potential equipment failure. Units must not be
located in the vicinity of steam, hot air or fume exhausts. Adequate
air circulation through the condensing unit is critical to ensure proper
equipment operation. Improper installation can damage the unit and will
void the warranty.
penthouse-style packaged units are designed
for indoor use only in ambient temperatures of 50°F to 100°F. The unit
cabinet is not approved for weather tight applications.
Another important consideration is that the unit should be mounted
away from noise sensitive spaces and must have adequate support to
avoid vibration and noise transmission into the building. Storage should
not be allowed on top of walk-in structure. Unit must not be enclosed
in an unventilated space.
Figure 1.
System Space and Location Requirements for
PTN models
Side View
Minimum 2" clearance from
opening to adjacent wall. No
storage is allowable on top of
walk-in structure.
IMPORTANT: Ventilation air
must be provided for the
condensing unit.
Structure must not be masked
to building ceiling, blocking air
flow to unit.
Top View
Two
Systems
PTN Models
4
Allow 2 feet
clearance above
unit to remove
top panel and
to allow service
access.
Mounting rails
may be used to
attach unit to
ceiling.Through-
bolts should
be insulated or
non-conductive
to prevent
sweating.
Evaporator
Section
2 x Width
W
Compressor
Section
Min.
Min.
Evaporator
Airflow
W = Unit Width
Installation and Operations Manual

Recommended Unit Placement

Some general rules for the evaporator section placement which
must be followed are:
1.
Ensure that the structural integrity of the box can
withstand the weight of the top mounted equipment.
2.
The air pattern must cover the entire room.
NEVER locate the evaporator section over doors.
3.
4.
Location of aisles, racks, etc. must be known.
5.
Never remove or unlock any panel cam-locks to
install top mounted equipment.
The size and shape of the storage will generally determine the type
and number of units to be used and their location.
Top View
One
Evaporator
Compressor
Evaporator
Airflow
Evaporator
Section
W
Compressor
Min.
Section
Evaporator
Airflow
System
Section
Section
Multiple units must be spaced
properly to provide adequate air
circulation.
NOTE:
Always avoid
placement of units
directly above doors
and door openings.