Rapid Parameter Set Selection (EZY)
The easy controller features the EZY parameter which is used to
quickly choose a list of parameters, with corresponding values, for
the control of the refrigeration system.
Table of Alarms and Signals
When an alarm is activated, the display shows the corresponding
message that flashes alternating with the temperature; if fitted and
enabled, the buzzer and the alarm relay are also activated.
All the alarms have automatic reset (that is, they stop when
the causes are no longer present), except for alarm 'CHt' which
has manual reset (instrument on/off using the UP button or by
disconnecting the power supply).
Alarm
Buzzer and Alarm Relay
Code
E0
active
E1
not active
E2
not active
IA
active
dOr
active
LO
active
HI
active
EE
not active
EF
not active
Ed
not active
dF
not active
cht
not active
CHt
active
EtC
not active
LED
Alarm Description
ON
probe 1 error= control
ON
probe 2 error= defrost
ON
probe 3 error= condenser/ product
ON
external alarm
ON
open door alarm
ON
low temperature alarm
ON
high temperature alarm
ON
unit parameter error
ON
operating parameter error
ON
defrost ended by timeout
OFF
defrost running
ON
dirty condenser pre-alarm
ON
dirty condenser alarm
ON
clock alarm
NOTE:
• to restore the selected rapid parameter set at any time, turn the
controller off and on again, while holding SET. The display shows
"CE" to indicate that the selected rapid set (EZY= 1, 2, 3) has again
overwritten the operating parameters, thus restoring the original
set of parameters;
• to restore all the parameters and return to the original default
values (factory settings), turn the controller off and on again
while holding DOWN and SET, until the display shows "CF". Use
this procedure with extreme care, as it may compromise the
fundamental control settings;
• EZY=0 brings no change;
Pressing the SET button mutes the buzzer, while the
code displayed and the alarm relay only go off when
the causes of the alarm have been resolved. The alarm
codes are shown in the table below:
Reset
automatic
automatic
automatic
automatic
automatic
automatic
automatic
not possible
manual
on first defrost ended correctly
automatic
automatic
manual
by setting the time
Enable Alarm
parameters involved
d0= 0 / 1 / 4, F0= 1
[A4=10]
[A4 = 1] [+A7]
[A4 = 7/8][+A7]
[AL] [Ad]
[AH] [Ad]
[dP] [dt] [d4] [A8]
[d6=0]
[A4=10]
[A4=10]
if bands active
13