Test Operation; Unit Status; Operating Hours; Contact Information - Daikin BRC1H81W7 Installer And User Manual

Wired remote controller
Hide thumbs Also See for BRC1H81W7:
Table of Contents

Advertisement

15 Maintenance

14.5.38 Test operation

Perform an indoor unit test operation. During the test run, the indoor
units cycle through various operation modes and functions to check
if they are ready for operation.
When
Only activate the test operation after the following is completed:
▪ Installation of refrigerant piping;
▪ Installation of drain piping;
▪ Connection of electrical wiring.
Typical workflow
Performing a test operation typically consists of the following stages:
1
Activating the test operation (Madoka Assistant app),
2
Testing the indoor unit functions according to the instructions
set out in
"To perform a test operation" on
3
Deactivating the test operation (Madoka Assistant app),
4
Checking the error history for possible errors.
5
If applicable, fixing the causes of those errors.
6
Repeating the procedure if required.
INFORMATION
This function is only available for Sky Air indoor units.
INFORMATION
Also see the installation manual of the indoor unit and
outdoor unit.
Precautions when performing a test operation
CAUTION
Before starting up the system, make sure:
▪ The indoor and outdoor unit wiring is completed.
▪ The switch box covers of the indoor and outdoor units
are closed.
NOTICE
Be sure to turn on the power 6 hours before operation in
order to have power running to the crankcase heater and
to protect the compressor.
INFORMATION
After the installation of the refrigerant piping, drain piping,
and electrical wiring, make sure to clean the inside of the
indoor unit, as well as the decoration panel.
To perform a test operation
1 Confirm that the indoor unit gas and liquid stop valves are open.
INFORMATION
It is possible that the pressure inside the refrigerant circuit
does not rise, despite the opened stop valve. This can be
due to the expansion valve (or the like) blocking the
refrigerant, and does not obstruct the test run.
2 Open the Madoka Assistant app.
3 Navigate to the operation screen of the controller that is
connected to the indoor unit(s) on which you want to perform a
test run.
4 In the operation screen, set the operation mode to Cooling.
5 Go to the "Unit settings" menu (upper right corner of the
operation screen).
Result: You are in the "Unit settings" menu.
6 In the "Maintenance field", tap "Test operation".
Installer and user reference guide
44
7 Tap "Start test operation".
8 Return to the operation screen.
9 Tap "Vertical airflow direction".
10 Tap "Fixed".
11 Cycle through the five fixed airflow directions, and confirm if the
12 Return to the "Test operation" menu.
13 Tap "Stop test operation".
14 Go to
page 44,
15 Check the error history. If required, solve the cause of the errors

14.5.39 Unit status

With Unit status, you can:
▪ Information retrieval: enter a code to make the system retrieve
specific information about an indoor or outdoor unit component.
First select a unit by way of its unit number, then enter the code to
start the information retrieval.
▪ Indoor unit: see information provided by various sensors that are
present in the system. First select a unit by way of its unit number.

14.5.40 Operating hours

Monitor indoor and outdoor unit operating hours.

14.5.41 Contact information

Enter the phone number of the system's service contact.

14.5.42 Active airflow circulation

Enable Active airflow circulation to have a more even temperature
distribution in the room.
When Active airflow circulation is enabled, indoor unit fan speed and
airflow direction get controlled automatically, making manual fan
speed and airflow direction changes impossible.
15
15.1
Result: You are in the "Test operation" menu.
Result: The indoor unit(s) enter test operation mode, during
which normal operation is not possible.
indoor unit flaps behave correspondingly.
Result: The indoor units leave test operation mode. Normal
operation is possible again.
"12  Operation"  on page  16
unit(s) behave according to the information set out there.
and perform the test operation again.
INFORMATION
The test operation finishes after 30 minutes.
INFORMATION
The information retrieval function is only present in the
menu when you use the app in installer mode. For
instructions on how to activate installer mode, see
"14.3 Installer mode" on
page 35.
Maintenance

Maintenance safety precautions

WARNING
Before carrying out any maintenance or repair activities,
stop system operation with the controller, and turn off the
power supply circuit breaker. Possible consequence:
electric shock or injury.
and confirm if the indoor
BRC1H81W+S7
Wired remote controller
4P513690-1C – 2019.05

Advertisement

Table of Contents
loading

This manual is also suitable for:

Brc1h81s7

Table of Contents