TZIDC, TZIDC-200 DIGITAL POSITIONER | TD/TZIDC/TZIDC-200/NON-CONTACT_SENSOR-EN REV. A

Manual configuration of the parameters

Note
For detailed information on the parameterization, consult the
separate configuration and parameterization instructions
"COI/TZIDC/TZIDC-200".
The following parameters must be configured:
Parameter
Description
Selection of actuator type
ROTARY: Part-turn actuator
LINEARY: Linear actuator
Operating range end position minimum
Operating range end position maximum
Rotational direction of the spring effect or
rotational direction at OUT2 under pressure.
CLOCKWISE: Rotational direction clockwise
CTCLOCKWISE: Rotational direction
counterclockwise
Rotational direction to reach 0% position of the
actuator.
CLOCKWISE: Rotational direction clockwise
CTCLOCKWISE: Rotational direction
counterclockwise
NOTICE
Damage of actuators / valves or impairment of the regulator
function
In cases of incorrect parameterization, in particular of
parameter P6.3 (SPRNG_Y2) and P6.7 (ZERO_POS), damage to
actuators/valves or an impairment of the regulator function
may occur.
Ensure that the configuration of parameters is performed
in accordance with the following method.

Procedure

1. Activate the safety position via parameter P11.0 (FAIL_POS).
2. Reset the positioner via parameter P11.1 (FACT_SET) to the
factory setting.
3. Save the changes via parameter P11.5 (EXIT) in the non-
volatile memory.
4. Select the actuator type via parameter P6.2 (ACTUATOR).
ROTARY: Rotary actuator or gear rack actuator.
LINEARY: Linear actuator
5. Select parameter P6.0 (MIN_VR).
Move the actuator by pressing the  button to the 0%
position (OUT1 depressurized).
Press and hold the ENTER button until the countdown is
finished (MIN_SET). The position is copied as MIN_VR.
Briefly press the ENTER button. The set limit value is
displayed for 2 seconds (MIN_SAVE).
Note the rotational direction
(clockwise/counterclockwise) of the actuator and
whether the actuator rotates into the 0% direction
(yes/no).
6. Select parameter P6.1 (MAX_VR).
Move the actuator by pressing the  button to the 100%
position (OUT2 depressurized).
Press and hold the ENTER button until the countdown is
finished (MAX_SET). The position is copied as MAX_VR.
Briefly press the ENTER button. The set limit value is
displayed for 2 seconds (MAX_SAVE).
7. Select parameter P6.7(ZERO_POS).
If the actuator is moved into the 0% position when
configuring P6.0 (MIN_VR), position the parameter in the
relevant rotational direction (CLOCKWISE /
CTCLOCKWISE).
8. Select parameter P6.3(SPRNG_Y2).
Now position the parameter in the rotational direction
determined during the configuration of P6.0 (MIN_VR)
(CLOCKWISE / CTCLOCKWISE).
9. Select parameter P6.8 (EXIT) to return to the operational
level.
Select NV_SAVE to save the configurations in the non-
volatile memory.
Select CANCEL to reject the configurations in the non-
volatile memory.
10. Check the activation of the actuator. If the control behavior is
incorrect, check the parameterization in accordance with
these instructions and perform it again if required.