Trane YZJ150 Installation, Operation And Maintenance Manual page 18

Packaged rooftop air conditioners precedent cooling and gas/electric
Table of Contents

Advertisement

Dimensions and Weights
Clearances
Figure 10, p. 18
illustrates the minimum operating and
service clearances for either a single or multiple unit
installation. These clearances are the minimum distances
necessary to assure adequate serviceability, cataloged unit
Figure 10. Typical installation clearances for single and multiple unit applications
Notes:
1. When equipped with economizer
or barometric relief damper, clearance
distance is to be measured from
protruding hood instead of base.
2. Clearance is the same if any unit
is rotated 180 .
Weights
Table 1. Model weights, corner weights (lbs) and center of gravity dimensions (in.)
Tons
Unit Model No.
12.5
YZJ150
15
YZJ180
17.5
YZJ210
20
YZJ240
25
YZJ300
(a)
Weights are approximate. Weights do not include additional factory or field installed options/accessories. For option/accessory additional weights to be added to unit weight,
reference the following table.
(b)
Corner weights are given for information only.
18
Side by Side
Note 1
7'0"
2134 MM
4'0"
1219 MM
Model Weights
(a)
Shipping
Net
2341
2121
2346
2126
2446
2226
2451
2231
2454
2234
capacity, and peak operating efficiency. Providing less than
the recommended clearances may result in condenser coil
starvation, "short-circuiting" of exhaust and economizer
airflows, or recirculation of hot condenser air.
6'0"
1829 MM
Single Unit
3'0"
5'8" With economizer/damper
914 MM
1727 MM
Corner Weights
A
B
651
544
652
545
718
562
719
563
720
564
End to End
Note 1, 2
5'0"
1525 MM
3'0" Without economizer/damper
914 MM
(b)
Center of Gravity (in.)
Length
C
D
422
505
56
423
506
56
416
531
54
417
532
54
417
533
54
Width
38
38
37
37
37
RT-SVX077B-EN

Advertisement