Electrical connection
7.1.1

Connect the PE wire

Terra 360
A
7.2

AC input

7.2.1

Supported low voltage network types

The following network configurations are permitted for the connection of this EV supply equipment (EVSE):
• TN-C
• TN-C-S
• TN-S
• TT
Terra 60
B
A
B
• Cut the cables to the correct length and install cable
lugs.
• Install the Main Protective Earth (PE) cable (A) to the PE
busbar (identified by the PE symbol).
NOTE
The Terra 360 model has an additional PE
busbar to connect the big size cable in
vertical position.
Cable lug
Hole
for a M10 bolt (Ø11)
• If it is necessary or is required by local rules, install the
Second Protective Earth (PE) cable (B) to the PE busbar
(identified by the PE symbol).
Cable lug
Hole
for a M10 bolt (Ø11)
• Tighten the fasteners to the following torque:
PE (Yellow/Green)
57
Torque (Nm)
50...55