Suction Pressure +- 2 lb.
Water Temperature
50°
50°
18
60°
20
70°
20
80°
21
90°
23
105°
27
R
S
EFRIGERATION
A complete understanding of the icemaker and hermetic refrigeration system is necessary before any
adjustments are made. The refrigeration technician must use high and low side pressure readings, water
and air temperatures, plus general conditions of cleanliness to assess the refrigeration system status
when making any adjustments.
All icemaker products are tested and adjusted at the factory prior to shipment where the ambient
temperature ranges from 650F to 900F, depending on the season of the year.
Whenever a new icemaker is initially installed and started-up, it is imperative that the start-up operator
make the following checks and readjustments for local conditions.
P
C
UMPDOWN
YCLE
The Series1400 unit is a split system. The icemaker consists of two gearmotor/evaporator assemblies
and a liquid line solenoid. The condensing unit consists of a compressor, condenser, fan motor and
receiver. The icemaker is designed for indoor use only. The condensing unit is designed for outdoor use.
The two units are connected with a precharged line kit.
The system operates on a pump down cycle. When the bin thermostat senses ice it opens the circuit to
the liquid line solenoid. The liquid line solenoid closes and stops the flow of refrigerant to the
evaporators. This causes the suction pressure to drop. The condensing unit is shut off when the suction
pressure drops below 5 psig. The low-pressure control should be adjusted to open between 0-5 psig and
close between 15-20 psig. Note: there is no electrical connection between the two units.
E
V
XPANSION
ALVE
You will find a thermal expansion valve on icemakers, which is used to control the amount of refrigerant
flowing through the evaporator. Improperly installed or defective expansion valves may cause low
production, soft ice, squeaking from evaporator and excessive load inside evaporator.
By using general refrigeration trouble shooting along with the pressure charts, you can easily determine
whether or not the expansion valve is working properly.
NOTE: Units with thermostatic expansion valve, the valve is located on bottom refrigerant line.
Sensing bulb is located on top refrigerant line.
Very high discharge pressure is present in system. Quick disconnects on your gages will minimize
Danger and loss of refrigerant. Comply with federal regulations for reclaiming refrigerant.
© 2006-2008, IMI Cornelius Inc.

REFRIGERATION SYSTEM

70°
90°
18
18
20
20
20
20
21
21
23
23
27
27
A
YSTEM
DJUSTMENTS
- 9 -
Continuous Flow Icemaker Service Manual
Discharge Pressure +- 10 lbs.
Water Temperature
50°
50°
213
60°
220
70°
225
80°
230
90°
251
105°
302
Publication Number: 630460324SER