Siemens RVP331 Installation Instructions Manual page 6

Heating controller
Table of Contents

Advertisement

Line Function, display
66 Type of optimisation
67 Max. heating up time
68 Max. early shutdown
69
Max. limitation of the room tem-
perature
70 Room temperature influence
71 Room temperature setpoint boost
with boost heating
Block «Pump heating circuit»
75 Overtemperature protection pump
heating circuit
Block «Actuators heating circuit»
81 Max. limitation of the flow tempera-
ture
82 Min. limitation of the flow tempera-
ture
83* Max. limitation of the flow tempera-
ture
84* Excess flow temperature mixing
valve / heat exchanger
85* Actuator running time
86* P-band of control (Xp)
87* Integral action time of control (Tn)
88* Type of actuator
89* Switching differential
* Operating lines 83 to 89: with plant type 6–x, only heating circuit 2 can be selected!
Block «Boiler»
91 Boiler operating mode
92 Max. limitation of the boiler tem-
perature
93 Min. limitation of the boiler tem-
perature
94 Switching differential of boiler
95 Min. limitation of burner running
time
96 Release limit burner stage 2
97 Reset limit burner stage 2
98 Locking time burner stage 2
99 Operating mode pump M1
Block «Setpoint of return temperature limitation»
101 Setpoint of return temperature
limitation, constant value
6/8
31.01.2006
Default
Range
0
0 / 1
00:00 h
00:00...42:00
0:00 h
0:00...6:00
--.-
--.- or
0...35
4
0...20
5 °C
0...20
1
0 / 1
---
--- or
0...140
---
--- or
0...140
---
--- or
1...600
10 °C
0...50
120 s
30...873
32.0 °C
1...100
120 s
10...873
1
0 / 1
2 °C
1...20
0
0...2
95 °C
25...140
10 °C
5...140
6 °C
1...20
4 min
0...10
50
0...500
°C
min
*
10
0...500
°C
min
*
20 min
0...40
1
0 / 1
---
--- or
0...140
CE1G2478en
74 319 0165 0 a
Setting
Explanations, notes and tips
0 = with room model
........
........
1 = with room unit / room sensor
Setting 0 only permits optimum start
control
Max. forward shift of switching on be-
........ h ........ h
fore occupancy starts.
Setting 00:00 = no optimum start con-
trol
Max. forward shift of switching off be-
........ h ........ h
fore occupancy ends.
Setting 0:00 = no optimum stop control
Input --.- = limitation inactive.
........ °C ........ °C
Function can only be provided with
room unit / room sensor
Gain factor for influence of the room
........
........
temperature.
Function can only be provided with
room unit / room sensor
....... °C ....... °C
not ad-
0 = function inactive
justable
......
1 = function active
Input --- = function inactive
....... °C ....... °C
No safety function!
Input --- = function inactive
........ °C ........ °C
Input --- = function inactive
..... °C/h ..... °C/h
(function prevents cracking noise)
Excess flow temperature for primary
....... °C ....... °C
controller in interconnected plants
...... s
...... s
Settings required only for three-position
....... °C ....... °C
actuator
...... s
...... s
0 = two-position control
........
........
1 = three-position control
Setting required only for two-position
....... °C ....... °C
actuator
0 = with manual shutdown (button
........
1 = with automatic shutdown (OFF,
when there is no demand for heat)
2 = without shutdown
No safety function!
....... °C
....... °C
....... °C
....... min
........
°C
min
*
........
°C
min
*
....... min
0 = without shutdown in the case of
.......
protective boiler startup
1 = with shutdown in the case of protec-
tive boiler startup
Input --- = function deactivated
....... °C