Rack requirements

To mount the switch in a 19-inch rack, the rack must meet the requirements in Table2-2.
Figure2-3 S9820-8C/S9820-8C-SAN chassis dimensions
1
50 mm (1.97 in)
(1) Fan module handle
Table2-2 Rack requirements
Switch model
S9820-8C
S9820-8C-SAN
IMPORTANT:
To reserve enough cabling space and close the rack door easily, make sure the rack meets the
depth requirements.

Installation accessories

Table2-3 Installation accessories for rack-mounting the switch
Item
Mounting bracket (provided)
760 mm
(29.92 in)
Chassis dimensions
Height—130.5 mm (5.14 in)/3
RU
Width—440 mm (17.32 in)
Depth—837 mm (32.95 in)
760 mm (29.92 in) for the
chassis
27 mm (1.06 in) for the
interface module ejector
levers
50 mm (1.97 in) for the fan
module handles
Quantity and requirements
1 kit. See Figure2-4. The mounting bracket with a round hole in the
narrow flange supports hanging a fixed asset tag.
2-8
(2) Interface module ejector lever
Distance
between the
front and rear
rack posts
630 to 900 mm
(24.80 to 35.43 in)
2
130.5 mm (5.14 in)
27 mm (1.06 in)
Rack requirements
A minimum of 1200
mm (47.24 in) in
depth
(recommended)
A minimum of 150
mm (5.91 in)
between the front
rack post and the
front door.
A minimum of 840
mm (33.07 in)
between the front
rack post and the
rear door.