9. Safety and Control Device Setting

9. Safety and Control Device Setting
Compressor Protection
The compressor is protected by the following devices and their combinations.
1. High Pressure Switch: This switch cuts out the operation of the compressor when the discharge
pressure exceeds the setting.
2. Oil Heater: This band type heater protects against oil foaming during cold starting, as it is energized
while the compressor is stopped.
(Standard Type)
Model
For Compressor
Pressure Switches
High
Cut-Out
Cut-In
Fuse Capacity
3N~, 380-415V, 50Hz
3N~, 380V, 60Hz
Oil Heater Capacity
(pcs/unit)
CCP Timer
Setting Time
For DC Fan Module
Fuse Capacity
3N~, 380-415V, 50Hz
3N~, 380V, 60Hz
Model
For Compressor
Pressure Switches
High
Cut-Out
Cut-In
Fuse Capacity
3N~, 380-415V, 50Hz
3N~, 380V, 60Hz
Oil Heater Capacity
(pcs/unit)
CCP Timer
Setting Time
For DC Fan Module
Fuse Capacity
3N~, 380-415V, 50Hz
3N~, 380V, 60Hz
70
RAS-
RAS-
080CNCCLW
100CNCCLW
-0.05
MPa
4.15
4.15
-0.15
MPa
3.20 ±0.15
3.20 ±0.15
A
50
50
W
40.8 x 1
40.8 x 1
min.
3
3
A
10
10
RAS-
RAS-
200CNCCLW
220CNCCLW
4.15 -0.05
4.15 -0.05
MPa
-0.15
MPa
3.20 ±0.15
3.20 ±0.15
A
63
50
W
40.8 x 1
40.8 x 2
min.
3
3
A
10
10
RAS-
RAS-
120CNCCLW
140CNCCLW
Automatic Reset, Non-Adjustable
(each one for each compressor)
-0.05
-0.05
4.15
4.15
-0.15
-0.15
3.20 ±0.15
3.20 ±0.15
50
40.8 x 1
40.8 x 1
Non-Adjustable
3
10
RAS-
RAS-
240CNCCLW
260CNCCLW
Automatic Reset, Non-Adjustable
(each one for each compressor)
4.15 -0.05
4.15 -0.05
-0.15
-0.15
3.20 ±0.15
3.20 ±0.15
50
40.8 x 2
40.8 x 2
Non-Adjustable
3
10
RAS-
160CNCCLW
180CNCCLW
-0.05
-0.05
4.15
4.15
-0.15
-0.15
3.20 ±0.15
3.20 ±0.15
63
63
40.8 x 1
40.8 x 1
3
3
10
10
RAS-
280CNCCLW
300CNCCLW
4.15 -0.05
4.15 -0.05
-0.15
-0.15
3.20 ±0.15
3.20 ±0.15
63
63
40.8 x 2
40.8 x 2
3
3
10
10
RAS-
-0.05
-0.15
63
3
10
RAS-
-0.15
63
3
10