Potterton 36 Installation And Service Manual page 62

High efficiency wall hung condensing gas boiler
Table of Contents

Advertisement

9 Maintenance
Fig.65
Setting the gas valve
Reset
R
1
2
B
62
R
2
1
3
0
4
bar
A
PN-0000376
Setting the gas valve (CO
2
Important
The CO
must be only checked and adjusted to set the valve if a
2
suitable calibrated combustion analyser is available, operated by a
competent person.
See
Annual Servicing, page 55
1. The combustion (CO
2
several minutes. To do this it is necessary to set the boiler to "Calibra­
tion Mode" .
2. Ensure that all external controls are calling for heat. The actual current
boiler temperature is shown on the display.
3. Turn both control knobs fully anticlockwise, then quickly turn the right
1
hand knob
/
clockwise twice and back in quick succession (within 2
4
seconds). "304" will appear in the display screen.
4. Turn the left hand knob fully clockwise. "100" will appear in the display
screen, indicating maximum output.
1
Combustion test point
2
Incoming air for combustion test point
A
Throttle Adjustment Screw
B
Offset Adjustment Screw
5. Remove the plug from the flue sampling test point. Insert the analyser
probe and allow sufficient time for the reading to settle.
Potterton
Assure Combi
CO
% (maximum)
2
6. It is possible to alter the CO
the plastic cover from the Throttle Adjustment Screw. At maximum
rate the throttle adjustment screw should be turned, using a suitable
hexagon key, until the correct reading is obtained.
Turning clockwise will reduce the CO
Turning anticlockwise will increase the CO
7. The CO
must then be checked at minimum rate. Turn the left hand
2
knob fully anticlockwise. As the knob is turned the display will change,
indicating the fan speed. When the display reads "0" the boiler runs at
minimum rate.
Potterton
Assure Combi
CO
% (minimum)
2
8. With the boiler on minimum, the Offset Adjustment Screw must be al­
tered, using a suitable hexagon key, after removing the cap.
Turning clockwise will increase the CO
Turning anticlockwise will reduce the CO
9. The calibration function is maintained for 20 minutes unless the maxi­
mum central heating temperature is exceeded. The function can be
disabled at any time by turning the right hand knob.
10. Check the combustion performance (CO/CO
than 0.004.
)
) may be checked after running the boiler for
25 - 30 - 36
9.0 + 0.3 – 0.2
by adjustment of the gas valve. Remove
2
.
2
.
2
25 - 30 - 36
8.5 + 0.1 — 0.4
.
2
.
2
ratio). This must be less
2