Product Specifications - Trane 4YCY4036 Installation And Operation Manual

Single packaged gas/electric 14 seer convertible, 2-5 ton 60-115 mbtu r-410a
Table of Contents

Advertisement

Product Specifications

MODEL
RATED Volts/PH/Hz
Performance Cooling BTUH
(a)
Indoor Airflow (CFM)
Power Input (KW)
EERH/L/SEER BTU/Watt-Hr
Sound Power Rating [dB(A)]
(b)
PERFORMANCE HEATING
(c)
Input BTUH- 1st Stage (N.Gas)
Input BTUH- 2nd Stage (N.Gas)
AFUE
Temp Rise - Min/Max
Orifice QTY / Drill Size (N.G.)
POWER CONN. — V/Ph/Hz
Min. Brch. Cir. Ampacity
(e)
Fuse Size — Max. (amps)
Fuse Size — Recmd. (amps)
COMPRESSOR
VOLTS/PH/HZ
R.L. Amps — L.R. Amps
OUTDOOR COIL — TYPE
Rows/F.P.I
Face Area (sq. ft.)
Tube Size (in.)
Refrigerant Control
INDOOR COIL — TYPE
Rows/F.P.I
Face Area (sq. ft.)
Tube Size (in.)
Refrigeration Control
Drain Conn. Size (in.)
OUTDOOR FAN — TYPE
DIA. (IN.)
DRIVE/NO. SPEEDS
CFM @ 0.0 in. w.g.
(f)
Motor — HP/R.P.M
Volts/Ph/Hz
F.L. Amps/L.R Amps
INDOOR FAN — TYPE
Dia. x Width (in.)
Drive/No. Speeds
CFM @ 0.0 in. w.g.
(g)
Motor — HP / R.P.M.
Volts/Ph/Hz
F.L. Amps
COMBUSTION FAN — TYPE
Drive / No. Speeds
Motor – HP / R.P.M.
Volts/Ph/Hz
FILTER / FURNISHED
Type Recommended
Recmd. Face Area (sq. ft)
(h)
REFRIGERANT
Charge (lbs.)
Subcooling
(a)
Rated in accordance with AHRI Standard 210/240. AHRI standard rating conditions are: 80 D.B.67 W.B. entering air to indoor coil. 95 D. B. entering air to
outdoor coil.
(b)
Sound Power values are not adjusted for AHRI 270–95 tonal corrections.
(c)
Ratings shown are for elevations up to 2000 ft. For higher elevations reduce ratings at a rate of 4% per 1000 ft. elevation.
(d)
Convertible to LPG.
(e)
This value is approximate. For more precise value, see Unit Nameplate.
Standard Air — Dry Coil — Outdoor.
(f)
(g)
Based on U.S. Government Standard Tests.
(h)
Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per
manufacturer's recommendation with a clean resistance of 0.05" W.C.
18-EB27D1-13C-EN
4YCY4036*075 [*096]
38000
1210
12 / 14.2
69
(d)
56250 [72000]
75000 [96000]
80
30/60 [40/70]
2/#33 [3/#37]
15.49
4 / 15
3.5
23.4
3280
1/5 / 830
10 x 10
1/2 / Variable
4.0
I I n n t t r r o o d d u u c c t t i i o o n n , , U U n n i i t t I I n n s s p p e e c c t t i i o o n n a a n n d d S S p p e e c c i i f f i i c c a a t t i i o o n n
4YCY4048*096 [*120]
208-230/3/60
48500
1605
LOCATED ON UNIT NAMEPLATE
12 / 14.2
73
72000 [90000]
96000 [120000]
80
30/60 [40/70]
3/#37 [3/#32]
208-230/3/60
LOCATED ON UNIT NAMEPLATE
LOCATED ON UNIT NAMEPLATE
LOCATED ON UNIT NAMEPLATE
SCROLL
208-230/3/60
LOCATED ON UNIT NAMEPLATE
SPINE FIN
2 / 24
18.10
3/8
EXPANSION VALVE
PLATE FIN
3 / 15
5.0
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
28.2
DIRECT / 1
4470
1/4 / 825
208-230/3/60
LOCATED ON UNIT NAMEPLATE
CENTRIFUGAL
DIRECT / VARIABLE
See Fan Performance table
3/4 / Variable
208–230/1/60
LOCATED ON UNIT NAMEPLATE
CENTRIFUGAL
Direct / 2
1/45 / 2800/1500
208–230/1/60
NO
THROWAWAY
5.3
R-410
LOCATED ON UNIT NAMEPLATE
LOCATED ON UNIT NAMEPLATE
4YCY4060*
58500
1800
12 / 14
76
90000
120000
30 / 60
3 / #32
23.57
4 / 15
5.0
28.2
5730
1/3 / 830
11 x 10
1 / Variable
5.3
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

4ycy40484ycy4060

Table of Contents