Cased aluminum 'convertible' coils

Advertisement

Quick Links

Installer's Guide
18-AH44D1 -6
I llllll lllll llll lllllll lllll llll 111111111111111111111111111111111
Cased Aluminum
11
Convertible
11
Coils
4TXCB003CC3HCB
4TXCC007CC3HCB
4TXCB004CC3HCB
4TXCC008CC3HCC
4TXCC005CC3HCB
4TXCD009CC3HCC
4TXCC006CC3HCB
4TXCD01 OCC3HCC
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT-This Document is customer property and is to remain with this unit. Please return to service informa-
tion pack upon completion of work.
A
WARNING
HIGH PRESSURE HAZARD
Contains Refrigerant!
System contains oil and refrigerant under high
pressure. Recover refrigerant to relieve pressure
before opening the system. See unit nameplate
for refrigerant type. Do not use non-approved
refrigerants, refrigerant substitutes, or refriger-
ant additives.
Failure to follow proper procedures or the use
of non-approved refrigerants, subsittutes, or re-
frigerant additives could result in death, serious
injury, or equipment damage.
A. GENERAL
These coils are designed for use with an upflow, downfiow,
or horizontal furnace in combination with a heat pump or
cooling only outdoor section using R-410A REFRIGER-
ANT.
This equipment has been evaluated in accordance with the
Code of Federal Regulations, Chapter XX, Part 3280 or the
equivalent. "Suitable for Mobile Home use" The height of
the Furnace, Coil and discharge duct work must be 7 ft. or
less.
Inspection
Check carefully for any shipping damage. This must be
reported to and claims made against the transportation
company immediately. Check to be sure all major compo-
nents are in the unit. Any missing parts should be reported
to your supplier at once, and replaced with authorized parts
only.
B. APPLICATION INFORMATION
1.
FURNACE AND COIL
The coil MUST BE installed downstream (in the outlet air)
of the furnace. The coil apex can face into or away from the
direction of the airflow, depending on horizontal left or right
application.
These coils fit the 171h'', 21", and 241h'' "width furnaces
without any adapters in vertical upflow, downflow, or hori-
zontal left application. Horizontal right configuration
requires changes to the coil before installation (see
section D, numbers 5 and 6).
2. INDOOR UNIT AIRFLOW
Indoor unit must provide the required airflow for the heat
pump or cooling combinations approved for these coils.
IMPORTANT: Review your installation requirements.
Check the table on the outline drawings and note all
dimensions for your coil before beginning the installation.
C. RECOMMENDATION
1. If
a coil is part of the total system installation, use the
Installer's Guide packaged with the furnaces, and outdoor
sections, and comfort control for physically installing those
components.
2.
It
is recommended that the outline drawing be stud-
ied and dimensions properly noted and checked against
selected installation site. By noting in advance proper
clearance allowances for installation and possible future
service of the coil.
A341869P20