ABB TZIDC Manual page 29

Digital positioner
Table of Contents

Advertisement

TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. G
IECEx
Type of protection Ex i, intrinsic safety
Ex marking
Ex marking
Marking
Ex ia IIC T6 resp. T4...T1 Gb
Ex ib IIC T6 resp. T4...T1 Gb
Ex ic IIC T6 resp. T4...T1 Gc
Type Examination Test
IECEx TUN 04.0015X
Certificate
Type
Intrinsic safety 'i'
Standards
IEC 60079-0, IEC 60079-11
Special conditions
The power supply for the 'Feedback on the actuator
position using proximity switches (Pepperl & Fuchs SJ2-
SN)' circuit must be provided intrinsically safe in
accordance with the PTB 00 ATEX 2049 X certificate
according to application type 2.
It is only permissible to connect, disconnect, and switch
live circuits during installation or maintenance, or for the
purpose of carrying out repairs.
Note
It is considered very unlikely that a potentially hazardous
atmosphere would be present in Zone 2 at the same time
that installation or maintenance or repair work was being
carried out.
Only non-flammable gases must be used for pneumatic
power supply.
When used with gases from group IIA and a temperature
class of T1 for pneumatic power supply, the positioner
TZIDC may only be used outdoors or inside sufficiently
ventilated buildings.
For TZIDC, the gas supplied must be kept sufficiently free
of air and oxygen to prevent an ignitable atmosphere
from forming. The exhaust gas must always be
discharged outside.
Only use suited cable entries that meet the requirements
of EN 60079-11.
Temperature Data
Temperature class
T4 to T1
T6*
*
When using the 'Plug-in module for digital feedback' in temperature
class T6, the maximum permissible ambient temperature range is -
40 to +35 °C.
Electrical Data
In type of protection 'Intrinsic safety Ex ib, Ex ia or Ex ic', only
for connection to a certified intrinsically safe circuit.
Current circuit (terminal) Electrical information (maximum values)
Signal circuit
U
= 30 V
i
(+11 / -12)
I
= 320 mA
i
P
= 1.1 W
i
Contact input
U
= 30 V
i
(+81 / -82)
I
= 320 mA
i
P
= 1.1 W
i
Switch output
U
= 30 V
i
(+83 / -84)
I
= 320 mA
i
P
= 500 mW
i
Local communication
Only for connection to a programming device
interface (LCI)
using an ABB LCI adapter (Um ≤ 30 V DC)
outside the hazardous area.
The following modules may be operated as an option:
Current circuit (terminal) Electrical information (maximum values)
Feedback on the
For maximum values, see certificate IECEx PTB
actuator position using
11.0092X Pepperl & Fuchs Type 2 proximity
proximity switches,
switches
(Pepperl & Fuchs SJ2-SN)
(Limit1: +51 / −52),
(Limit2: +41 / -42)
Plug-in module for
U
= 30 V
i
digital feedback
I
= 320 mA
i
(+51 / -52)
P
= 250 mW
i
(+41 / -42)
Plug-in module for
U
= 30 V
i
analog feedback
I
= 320 mA
i
(+31 / -32)
P
= 1.1 W
i
29
Ambient temperature Ta
−40 to +85 °C
−40 to 40 °C*
C
= 6.6 nF
i
L
= negligibly small
i
C
= 14.5 nF
i
L
= negligibly small
i
C
= 14.5 nF
i
L
= negligibly small
i
Ci = 3.7 nF
Li = negligibly small
Ci = 6.6 nF
Li = negligibly small