OPERATION: Refrigeration
There are two separate refrigeration systems in this machine.
The refrigeration system under low condenser air
temperatures is much the same as it is under
higher temperatures, with the exception that the
resulting low head pressures cause the head
pressure control to close off the liquid line
between the condenser and the receiver.
Head Pressure Control Valve - Low
Temperature
From
Compressor
From Condenser
During the pump down cycle (usually initiated by
the circuit board de-energizing the liquid line
valve) the discharge gases flow through their
normal path to the remote condenser, through the
head pressure control, and into the receiver.
Low Condensing Temperature
Valve
Disk
To
Receiver
PUMP DOWN
March 1995
Page 19
NME1850R & FME2400R
This forces more refrigerant into the condenser
(with a small amount of discharge gas going into
the receiver to maintain pressure until the head
pressure is built back up to the rated gauge
pressure of 180 psig). At that pressure the valve
opens up the liquid line from the condenser to the
receiver.
Head Pressure Control Valve - Normal
Temperature
From
Compressor
From Condenser
At this point the refrigerant flow is stopped by the
closed liquid line valve. This action forces the
refrigerant into the receiver and keeps it out of the
compressor. The pump down continues until the
low pressure control turns the compressor off.
Valve
Disk
To
Receiver