Connecting Multiple Units

5.4 Connecting Multiple Units
Two or more HPFF8s can be connected to each other to provide additional NAC extenders for a system; see wiring in Figures 5.5–5.10.
Maintain separation of power-limited and nonpower-limited wiring as discussed in Section 2.6 on page 24.
NOTE: Multiple units should not be connected in a "daisy chain" fashion. DO NOT connect a NAC output of one unit to the initiating device
signal input of the next unit. The synchronization signal will not pass unimpeded through multiple units with this wiring method.
HPFF8 System Connections
FACP
conventional
TB2
LEDs
HPFF8 Sync
Generator or
Pass-Through
(Slave)
J1
(filtered if
FWR input)
TB1
TB4
BATT+ BATT–
A+
A–
1L1
1L2
2L1
NAC Outputs
to NACs
Remote Sync or NAC
TB2
LEDs
HPFF8
Pass-Through
(Slave)
J1
(filtered if
FWR input)
TB1
TB4
BATT+ BATT–
A+
A–
1L1
1L2
2L1
2L2
3L1
to NACs
Ref +
Ref -
In #1 +
In #1 -
Out #1 +
Out #1 -
In #2 +
In #2 -
Out #2 +
Out #2 -
HPFF8(E)/HPFF8CM(E) NAC Expander — P/N 53499:B4 10/1/2018
Remote Sync
or NAC
Output
TB2
SW2
LEDs
TB3
J1
ELR or to
next units
J2
TB1
2L2
3L1
3L2
4L1
4L2
BATT+ BATT–
NAC Outputs
Figure 5.5 Typical System Connections
Output with sync
TB2
SW2
LEDs
HPFF8
TB3
Pass-Through
(Slave)
J1
(filtered if
FWR input)
J2
TB1
TB4
3L2
4L1
4L2
BATT+ BATT–
A+
A–
1L1
1L2
2L1
2L2
3L1
NAC Outputs
to NACs
Figure 5.6 System Sync Connections
TB3
in from FACP or
+
previous FF8
-
ELR or out
to next unit
Figure 5.7 Class B Input Connections
NAC Outputs
FACP
non-silenceable
conventional
silenceable
SW2
HPFF8 Sync
TB3
Generator or
Pass-Through
(Slave)
(filtered if
FWR input)
ELRs or to
next units
J2
TB4
A+
A–
1L1
1L2
2L1
2L2
3L1
3L2
4L1
4L2
to NACs
TB2
SW2
LEDs
HPFF8
TB3
Pass-Through
(Slave)
J1
(filtered if
FWR input)
J2
TB1
TB4
3L2
4L1
4L2
BATT+ BATT–
A+
A–
1L1
1L2
2L1
2L2
3L1
NAC Outputs
to NACs
TB3
Ref +
Ref -
in from FACP or
In #1 +
+
previous FF8
-
In #1 -
Out #1 +
Out #1 -
In #2 +
In #2 -
ELR or out
Out #2 +
to next unit
Out #2 -
FACP
TB2
SW2
LEDs
HPFF8 Sync
TB3
Generator or
Pass-
J1
Through
(Slave)
ELRs
or to
J2
next
TB1
TB4
BATT+ BATT–
A+
A–
1L1
1L2
2L1
2L2
3L1
3L2
4L1
4L2
units
NAC Outputs
to NACs
TB2
SW2
LEDs
HPFF8
TB3
Pass-Through
(Slave)
J1
(filtered if
FWR input)
J2
TB1
TB4
3L2
4L1
4L2
BATT+ BATT–
A+
A–
1L1
1L2
2L1
2L2
3L1
NAC Outputs
to NACs
TB3
Ref +
Ref -
In #1 +
In #1 -
Out #1 +
Out #1 -
In #2 +
In #2 -
Out #2 +
Out #2 -
Applications
SLC
Control Module (non-
silenceable point)
Relay Module
(silenceable
point)
SW2
TB3
ELR or to
J2
next unit
3L2
4L1
4L2
+
in from FACP or
-
previous FF8
ELR or out
to next unit
+
in from FACP or
previous FF8
-
ELR or out
to next unit
39

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hpff8eHpff8cmHpff8cme

Table of Contents