Connecting the HPF602ULADA to a FACP

Figure 4-2 shows the general layout of the HPF602ULADA PC board. This section also provides specific wiring
details for accessories.
Figure 4-2 The Model HPF602ULADA PC Board Layout
Consult the installation manual for specific wiring information for the control panel being used.
4.4.1

Common Trouble Relay

The HPF602ULADA has a Form C trouble relay built into Terminals 11-13. The relay provides a normally open
and a normally closed contact, both of which are rated at 2.5A. The trouble relay will deactivate under any
trouble condition.
A typical application of the trouble relay is to connect the HPF602ULADA normally closed (N.C.) contacts in
series with the EOL supplied with the fire alarm control panel. This will cause a trouble on the fire alarm control
panel when the HPF602ULADA opens its trouble contacts.