Circulator Blower Speeds - Amana MVM97 Installation Instructions Manual

Modulating gas furnace
Table of Contents

Advertisement

Circulator Blower Speeds

T
O AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK
OFF
TURN
POWER TO THE FURNACE BEFORE CHANGING SPEED TAPS
This furnace is equipped with an ECM circulator blower.
The heating blower speed is shipped set at "B", and the
cooling blower speed setting is "D". These blower speeds
should be adjusted by the installer to match the instal-
lation requirements so as to provide the correct heating
temperature rise and correct cooling CFM.
Use the dual 7-segment LED display adjacent to the DIP
switches to obtain the approximate airflow quantity. The
airflow quantity is displayed as a number on the display,
rounded to the nearest 100 CFM. The display alternates
airflow delivery indication and the operating mode indica-
tion.
Example: The airflow being delivered is 1225 CFM. The
display indicates 12. If the airflow being delivered is
1275, the display indicates 13.
1. Determine the tonnage of the cooling system installed
with the furnace. If the cooling capacity is in BTU/hr
divide it by 12,000 to convert capacity to TONs.
Example:
Cooling Capacity of 30,000 BTU/hr.
30,000/12,000 = 2.5 Tons
2. Determine the proper air flow for the cooling system.
Most cooling systems are designed to work with air
flows between 350 and 450 CFM per ton. Most man-
ufacturers recommend an air flow of about 400 CFM
per ton.
Example: 2.5 tons X 400 CFM per ton = 1000 CFM
The cooling system manufacturer's instructions must be
checked for required air flow. Any electronic air cleaners
or other devices may require specific quantity of air, con-
sult installation instructions of those devices for require-
ments.
3. Knowing the furnace model, locate the high stage
cooling air flow table. Look up the cooling air flow
determined in step 2 and find the required cooling
speed and adjustment setting.
Example:
A DM97MC0603BN** furnace installed with
a 2.5 ton air conditioning system. The air flow need-
ed is 1000 CFM. Looking at the cooling speed chart
for DM97MC0603BN**, find the air flow closest to 1000
CFM. A cooling airflow of 1000 CFM can be attained
by selecting the cooling speed "C" and the adjust-
ment to "normal".
WARNING
M odel
,
.
*MVM970603BN*
*MVM970803BN*
*MVM970804CN*
*MVM971005CN*
*MVM971205DN*
*CVM970603BN
*CVM970803BN
*CVM970804CN*
*CVM971005CN*
*100% CFM shown. CFM will vary proportionally with the gas valve BTU/H input.
4.
Continuous fan speed is selectable at 25%, 50%,
75% or 100% of the furnace's maximum airflow capability.
Example:
capability is 2000 CFM, the continuous fan speed
at 25% will be 0.25 x 2000 or 500 CFM.
5.
Locate the blower speed selection DIP switches on
the integrated control module. Select the desired "cool-
ing" speed tap by positioning switches 1 and 2 appro-
priately. Select the desired "adjust" tap by positioning
switches 9 and 10 appropriately. Refer to the DIP switch
chart for switch positions and their corresponding taps.
Verify CFM by noting the number displayed on the dual
7-segment LED display.
6.
The multi-speed circulator blower also offers sev-
eral custom ON/OFF ramping profiles for cooling. These
profiles may be used to enhance cooling performance and
increase comfort level. The ramping profiles are selected
using DIP switches 7 and 8. Refer to the bullet points be-
low for a description of each ramping profile. Verify CFM
by noting the number displayed on the dual 7-segment
LED display.
Low
High Stage
Tap
Stage
Cool
Cool
A
398
599
557
817
B
696
1007
C
810
1212
D
403
629
A
540
806
B
C
705
1023
819
1230
D
A
513
789
660
967
B
791
1182
C
913
1375
D
564
820
A
784
1133
B
982
1464
C
1259
1736
D
547
867
A
B
831
1160
1020
1467
C
D
1278
1910
433
656
A
541
790
B
686
972
C
806
1195
D
A
405
624
B
549
808
C
678
994
D
784
1177
A
556
837
714
1022
B
C
838
1206
991
1475
D
524
784
A
744
1078
B
927
1388
C
1185
1766
D
If the furnace's maximum airflow
100%
Low heat
Heat
CFM for
*CFM
2 stage
953
667
1059
740
1158
808
1260
881
1202
855
1316
923
1389
1033
1396
1063
1228
867
1337
939
1430
1016
1516
1077
1818
1256
1870
1292
1910
1316
1957
1358
1891
1329
1940
1362
1968
1390
2028
1440
938
687
950
751
986
814
992
874
1057
758
1146
815
1256
882
1349
946
1234
889
1325
944
1442
1019
1528
1068
1759
1209
1797
1249
1840
1277
1881
1300