10-4. FIXING HORIZONTAL VANE
Horizontal vane of each air outlet can be fixed according to the environment where it is installed.
Setting procedure
1) Turn off the main power supply (Turn off the breaker).
2) Remove the vane motor connector in the direction of the arrow shown below with pressing the unlocking button as in the
figure below.
Insulate the disconnected connector with the plastic tape.
Horizontal vane
3) Set the vertical vane of the air outlet by hand slowly within the range in the table below.
Measured standard
position of the grille
<Set range>
Angle θ = 21°
Standard of
horizontal position
(Horizontal)
1-9/16 inch
Dimension A
39 mm 
Note: Dimension between 1-9/16 inch
Caution
Do not set the dimension out of the range.
.
Erroneous setting could cause dew drips or malfunction of unit.
TCH118
Vane motor
θ
A
Horizontal vane
Angle θ = 24°
Angle θ = 39°
1-5/8 inch
41 mm
39 mm) and 1-15/16 inch (49 mm) can be arbitrarily set.
(
Connector
Angle θ = 42°
1-7/8 inch
1-29/32 inch
47 mm
48 mm
28
Vane motor
Unlocking button
Angle θ = 45°
(Downward)
1-15/16 inch
49 mm