Fan Control; Indoor Fan Control - Fujitsu RCG24KVLA Service Instruction

Split type room air conditioner cassette
Hide thumbs Also See for RCG24KVLA:
Table of Contents

Advertisement

3. Fan control

Tr: Room temperature
Ts: Setting temperature

3-1. Indoor fan control

¢ Fan speed
Indoor fan speed is defined as below.
Operation mode
Heating
Cooling/Fan
Dry
*1: Fan mode only
*2: Cooling mode only
¢ Fan operation
Airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH while indoor unit fan
only runs.
When fan mode is set at AUTO, it operates on MED fan speed.
¢ Cooling operation
Switch the airflow AUTO, and indoor fan motor will run according to room temperature, as below.
On the other hand, if switched in HIGH—QUIET, indoor motor will run at a constant airflow of COOL
operation modes QUIET, LOW, MED, HIGH as shown in "Fan speed" above.
Airflow change over (Cooling: Auto)
2°C
3-1. Indoor fan control
Cool air prevention
Tr - Ts ≥
2°C
> Tr - Ts ≥
1°C
1°C > Tr - Ts
When room
temperature drops
Fan mode
HIGH
MED+
MED
LOW
QUIET
S-LOW
HIGH
MED
LOW
QUIET
Soft quiet
S-LOW
Tr - Ts ≥
HIGH mode
2.5°C
MED mode
1.5°C > Tr - Ts
LOW mode
When room
temperature rises
- (04-7) -
Speed (rpm)
AUXG24KVLA
960
930
880
740
580
400
300
960
850
650
500
1
400*
2
300*
X zone: 500
J zone: 500
2.5°C
> Tr - Ts ≥
1.5°C
3. Fan control

Advertisement

Table of Contents
loading

This manual is also suitable for:

Auxg24kvlaAo g24kata seriesRog24kata

Table of Contents