Power supply
(cont.)
Types
201.D04
201.D06
201.D08
201.D10
201.D13
201.D16
Outdoor unit power supply 400 V~
!
Please note
Incorrect phase sequence can cause damage to
the appliance.
Make the compressor power supply only in the
phase sequence specified (see terminals) with a
clockwise rotating field.
GND Rx/Tx- Rx/Tx+
Modbus
C
Fig. 56
Outdoor unit wiring chamber: See "Opening the
A
outdoor unit wiring chamber".
Power supply 400 V/50 Hz
B
Separator (supplied)
C
Danger
Serious injury can be caused by electric current
and appliance damage can result if wires drift
into the adjacent voltage area.
It is essential to insert the separator supplied.
Cable
3 x 2.5 mm
3 x 2.5 mm
3 x 2.5 mm
3 x 2.5 mm
3 x 4.0 mm
3 x 2.5 mm
3 x 4.0 mm
3 x 2.5 mm
3 x 4.0 mm
L1
L2
L3
N
L1
L2
L3
N
PE
B
B
Max. cable length
2
29 m
29 m
2
29 m
2
20 m
2
Or
32 m
2
20 m
2
Or
2
32 m
20 m
2
Or
32 m
2
A
PE
Installation sequence
Max. fuse rating
B16A
B16A
B16A
B25A
B25A
B25A
59