Installation and operation manual
Split system air conditioners
Installation and operation manual
FDA200AXVEB
English
Split system air conditioners
FDA250AXVEB

Advertisement

Table of Contents
loading

Summary of Contents for Daikin FDA200AXVEB

  • Page 1 Installation and operation manual Split system air conditioners Installation and operation manual FDA200AXVEB English Split system air conditioners FDA250AXVEB...
  • Page 2 4P689940-5C...
  • Page 3 4P690931-8...
  • Page 4: Table Of Contents

    ▪ A subset of the latest technical data is available on the regional 15 Commissioning Daikin website (publicly accessible). 15.1 Checklist before commissioning..........18 ▪ The full set of latest technical data is available on the Daikin 15.2 To perform a test run..............18 Business Portal (authentication required). 16 Configuration 16.1...
  • Page 5: Specific Installer Safety Instructions

    ▪ Use flare nuts that are included with the unit. Using Make sure installation, servicing, maintenance, repair and different flare nuts may cause refrigerant gas leakage. applied materials follow the instructions from Daikin (including all documents listed in “Documentation set”) CAUTION...
  • Page 6: For The User

    3 User safety instructions WARNING Prevent hazards due to inadvertent resetting of the thermal cut-out: power to this appliance MUST NOT be supplied through an external switching device, such as a timer, or connected to a circuit that is regularly turned ON and OFF by the utility.
  • Page 7 3 User safety instructions ▪ In case of accidental refrigerant CAUTION leaks, make sure there are no naked NEVER expose little children, plants or flames. The refrigerant itself is animals directly to the airflow. entirely safe and non-toxic. R410A is WARNING a non-combustible refrigerant, and R32 is a mildly flammable refrigerant,...
  • Page 8 3 User safety instructions CAUTION flames, an operating gas appliance, or an operating electric heater). The room Before accessing terminal devices, size shall be as specified in the make sure to interrupt all power supply. General safety precaution. DANGER: RISK OF WARNING ELECTROCUTION ▪...
  • Page 9: About The System

    4 About the system About the system User interface WARNING CAUTION ▪ Do NOT modify, disassemble, remove, reinstall or ▪ NEVER touch the internal parts of the controller. repair the unit yourself as incorrect dismantling or ▪ Do NOT remove the front panel. Some parts inside are installation may cause an electrical shock or fire.
  • Page 10: Special Heating Operation Modes

    7 Maintenance and service Icon Operation mode NOTICE Fan only. In this mode, air circulates without heating ▪ Do NOT wipe the controller operation panel with or cooling. benzine, thinner, chemical dust cloth, etc. The panel may get discoloured or the coating peeled off. If it is Auto.
  • Page 11: To Clean The Air Outlet

    8 Troubleshooting ▪ If the dirt becomes impossible to clean, change the air filter. Clean with a soft cloth. If it is difficult to remove stains, use water or a neutral detergent. How to clean the air filter: 1 Remove the screws on the filter cover using screwdriver. About the refrigerant This product contains fluorinated greenhouse gases.
  • Page 12: Relocation

    Refer reference guide located https:// unusual occurs (burning smells etc.). www.daikin.eu for more troubleshooting tips. Use the search function to find your model. Leaving the unit running under such circumstances may cause breakage, electrical shock or fire. Contact your If after checking all above items, it is impossible to fix the problem dealer.
  • Page 13: Mounting The Indoor Unit

    12 Unit installation ▪ Ceiling insulation. When conditions in the ceiling exceed 30°C 12.2 Mounting the indoor unit and a relative humidity of 80%, or when fresh air is inducted into the ceiling, then additional insulation is required (minimum 10 mm 12.2.1 Guidelines when installing the indoor unit thickness, polyethylene foam).
  • Page 14: Guidelines When Installing The Ducting

    12 Unit installation 8 Insulate the ducts to prevent condensation from forming. Use INFORMATION glass wool or polyethylene foam 25 mm thick. Optional equipment. When installing optional equipment, also read the installation manual of the optional equipment. Depending on the field conditions, it might be easier to install the optional equipment first.
  • Page 15: Piping Installation

    13 Piping installation NOTICE The piping and other pressure-containing parts shall be suitable for refrigerant. Use phosphoric acid deoxidised seamless copper for refrigerant piping. ▪ Foreign materials inside pipes (including oils for fabrication) must be ≤30 mg/10 m. Refrigerant piping diameter Use the same diameters as the connections on the outdoor units: Drain pipe connection Refrigerant pipes Pipe outer diameter (mm)
  • Page 16: To Connect The Refrigerant Piping To The Indoor Unit

    14 Electrical installation 13.2.1 To connect the refrigerant piping to the NOTICE indoor unit Make sure to insulate all refrigerant piping. Any exposed piping might cause condensation. CAUTION Install the refrigerant piping or components in a position where they are unlikely to be exposed to any substance Electrical installation which may corrode components containing refrigerant, unless the components are constructed of materials that...
  • Page 17: To Connect The Electrical Wiring To The Indoor Unit

    14 Electrical installation Components User interface cable Only use harmonised wire providing double insulation and suitable for 70~90 applicable voltage 10~15 2-core cable Minimum size 0.75 mm Maximum length 500 m Recommended circuit 6 A breaker Residual current device MUST comply with national wiring regulation 14.2 To connect the electrical wiring to...
  • Page 18: Commissioning

    Next Do NOT interrupt the test run. commissioning instructions in this chapter, a general commissioning checklist is also available on the Daikin Business Portal (authentication required). Configuration The general commissioning checklist is complementary to the instructions in this chapter and can be used as a guideline and reporting template during commissioning and hand-over to the user.
  • Page 19: Technical Data

    5 After airflow automatic adjustment is finished (air conditioning unit will stop) check if the value number “—“ is set to 02. If there ▪ The full set of latest technical data is available on the Daikin is no change, perform the setting again.
  • Page 20 17 Technical data Symbol Meaning Symbol Meaning Symbol Meaning Earth Relay connector Switching power supply PTC* PTC thermistor Field wiring Short-circuit connector Insulated gate bipolar transistor Fuse Terminal (IGBT) Indoor unit Terminal strip Circuit breaker INDOOR Q*DI, KLM Earth leak circuit breaker Outdoor unit Wire clamp Overload protector...
  • Page 24 3P580564-1E 2022.11 Verantwortung für Energie und Umwelt...