Figure 41. Typical Battery Interface Connection – Common Battery System
Battery Aux Common
48 Vdc Battery Shunt Trip +
48 Vdc Battery Shunt Trip –
NOTE Battery Aux and DC Shunt Trip wiring should be a minimum of 18 AWG.
Figure 42. Typical Battery Interface Connection – Separate Battery System
Battery Aux
Battery Aux Return
48 Vdc Battery Shunt Trip +
48 Vdc Battery Shunt Trip –
NOTE Battery aux and DC shunt trip wiring should be a minimum of 18 AWG.
4 4 . . 9 9 . . 3 3 X X - - S S l l o o t t C C o o n n n n e e c c t t i i o o n n s s
NOTE
NOTE
For installation and setup of an X-Slot card, contact an Eaton service representative (see
To install wiring to connections:
UPS
TB1
5
Battery Aux
6
7
8
UPS
TB1
5
6
7
48 Vdc
8
LAN and telephone drops for use with X-Slot cards must be provided by the customer.
When installing external wiring to X-Slot cards, conduit must be installed to the UPS
cabinet. When installing internal wiring to X-Slot terminals, route the wiring through the
internal opening in the X-Slot communication bay.
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201764—Rev 14
Battery
Breaker or
Disconnect
ST
UPM 1
UPM 2
Battery
Battery
Disconnect
Disconnect
ST
ST
UPS System Installation
UPM 3
UPM 4
Battery
Battery
Disconnect
Disconnect
ST
ST
1.8 Getting
Help).
81