8
|
Piping installation
8.5.2 Formula to calculate the expansion vessel pre-pressure
8.5.3 To check the water volume and flow rate
Installer reference guide
78
▪
Domestic hot water tank – Standstills. In cases where during longer periods of
time there is no consumption of hot water, the equipment MUST be flushed with
fresh water before usage.
▪
Domestic hot water tank – Disinfection. For the disinfection function of the
domestic hot water tank, see
4
advanced" [
139].
▪
Thermostatic mixing valves. In accordance with the applicable legislation, it may
be necessary to install thermostatic mixing valves.
▪
Hygienic measures. The installation must be in compliance with the applicable
legislation and may require additional hygienic installation measures.
▪
Recirculation pump. In accordance with the applicable legislation, it may be
required to connect a recirculation pump in between the hot water end point
and the recirculation connection of the domestic hot water tank.
a
b
a Recirculation connection
b Hot water connection
c Shower
d Recirculation pump
The pre-pressure (Pg) of the vessel depends on the installation height difference
(H):
Pg=0.3+(H/10) (bar)
The indoor unit has an expansion vessel of 10 litre with a factory-set pre-pressure
of 1 bar.
To make sure that the unit operates properly:
▪
You MUST check the minimum and maximum water volume.
▪
You might need to adjust the pre-pressure of the expansion vessel.
Minimum water volume
There are no requirements for the minimum water volume.
INFORMATION
In critical processes, or in rooms with a high heat load, extra water might be
required.
"10.4.2 Domestic hot water control:
c
d
ERLA03DAV3 + EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1B – 2021.10